| 2017-03-06 09:26:10 | ****CORRECTIONS**** |
| | #17020797 - PAVING (INCLUDING RAMPS) |
| | #17020806 - CONVENIENCE STORE REMODEL (AND RELOCATION |
| | OF VACUUM?) |
| | #17020803 - NEW 6K DIESEL FUEL TANK AND 4 NEW FUEL |
| | DISPENSING ISLANDS |
| | #17030189 - CANOPY OVER FUEL DISPENSERS - SUBMIT |
| | APPLICATION |
| | |
| | ITEMS REQUIRING SEPARATE PERMITS, NOT REVIEWED AT THIS |
| | TIME (APPLICATION, PLANS, AND FEES): |
| | DUMPSTER ENCLOSURE |
| | CCTV |
| | SIGNAGE |
| | SITE LIGHTING (PROVIDE STRUCTURAL DETAILS, SITE PLAN |
| | AND CALCULATIONS FOR POLES AND FIXTURES) |
| | VERIFY WITH ZONING - A SEPARATE LANDSCAPING PERMIT MAY |
| | BE REQUIRED |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. PROVIDE A COPY OF THE CONTRACT FOR THIS PROJECT, FBC |
| | 109. THE VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD |
| | AND PROFIT, EVEN IF PROVIDED BY OTHERS. IF THIS IS A |
| | LABOR ONLY CONTRACT, PROVIDE THE INVOICES FOR THE |
| | MATERIALS AS WELL AS THE CONTRACT. |
| | |
| | PROVIDE VALUE FOR EACH PERMIT (17020797, 17020806, |
| | 17020803, 17030189). THE GRADING AND DRAINAGE VALUE |
| | SHOULD BE INCLUDED IN A SEPARATE ENGINEERING PERMIT, IF |
| | ENGINEERING DETERMINES THAT A SEPARATE ENGINEERING |
| | PERMIT IS REQUIRED. |
| | |
| | CONTACT THE ENGINEERING DEPARTMENT DIRECTLY TO |
| | DETERMINE IF A SEPARATE ENGINEERING PERMIT IS REQUIRED: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 2. PROVIDE A PERMIT APPLICATION FOR PERMIT 17030189, |
| | THE CANOPY. THE PERMIT APPLICATION SHOULD BE COMPLETE |
| | AND ACCURATE. THE QUALIFIER'S NAME SHOULD BE INCLUDED |
| | ON LINE "CONTRACTOR (CERT. HOLDER). QUALIFIER'S NAME |
| | SHOULD BE SPELLED CORRECTLY (PHILLIP). |
| | |
| | 3. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| | REQUIRED. THE PLANS ARE TO BE STAMPED AND THE RECEIPT |
| | SHOWING THAT FEES DUE HAVE BEEN PAID. THIS ITEM MAY BE |
| | ADDRESSED AFTER ALL PLAN REVIEWS ARE COMPLETE, BUT MUST |
| | BE ADDRESSED PRIOR TO PERMIT ISSUANCE. AN IMPACT FEE |
| | REVIEW STOP HAS BEEN ADDED TO 17020803. |
| | |
| | 4. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS, FS471, FAC61G15-23.002. THE PLANS SUBMITTED |
| | INCLUDE A DIGITAL SIGNATURE, WHICH CAN ONLY BE UTILIZED |
| | FOR DIGITAL SUBMITTALS. AS THIS IS A PAPER SUBMITTAL, |
| | SUBMIT TWO SIGNED, SEALED DATED ORIGINALS. |
| | |
| | 5. PROVIDE THE GEOTECHNICAL REPORT FOR THIS PROJECT, |
| | FBC 1803.5.2. THE REPORT SHOULD BE REVIEWED BY DOR |
| | PRIOR TO SUBMITTAL, FBC 107. |
| | |
| | 6. PLANS SHOW RELOCATION OF VACUUM. THIS WORK MAY BE |
| | INCLUDED IN THE RENOVATION PERMIT (17020806). EITHER |
| | INCORPORATE ALL INFORMATION FOR THIS FOR REVIEW, OR |
| | THIS PERMIT WILL BE ISSUED WITH PROVISO THAT A SEPARATE |
| | PERMIT, APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC |
| | 107. |
| | |
| | PLANS SHOW INSTALLATION OF A CCTV SYSTEM. THIS PERMIT |
| | WILL BE ISSUED WITH A PROVISO THAT A SEPARATE PERMIT, |
| | APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC 107. |
| | |
| | PLANS SHOW SITE LIGHTING. THIS PERMIT WILL BE ISSUED |
| | WITH A PROVISO THAT A SEPARATE PERMIT, APPLICATION, |
| | FEES, AND PLANS ARE REQUIRED, FBC 107. |
| | |
| | PLANS SHOW A DUMPSTER ENCLOSURE. THIS PERMIT WILL BE |
| | ISSUED WITH A PROVISO THAT A SEPARATE PERMIT, |
| | APPLICATION, FEES, AND PLANS ARE REQUIRED, FBC 107. |
| | |
| | ITEMS REQUIRING A SEPARATE PERMIT HAVE NOT BEEN |
| | REVIEWED AT THIS TIME. |
| | |
| | 7. PROVIDE PLANS FOR THE CONVENIENCE STORE RENOVATION. |
| | PLANS ARE TO INCLUDE WIND DESIGN CRITERIA, PRODUCT |
| | APPROVAL FOR THE PROPOSED NEW OPENING AND WINDOW, FBC |
| | 107, FBC 1603.1.4. |
| | |
| | WIND DESIGN CRITERIA WAS PROVIDED ON SHEET C0.0 BUT |
| | LACKS COMPONENT AND CLADDING DESIGN PRESSURE |
| | INFORMATION. |
| | |
| | A DETAIL WAS PROVIDED ON SHEET G1.0 BUT LACKS |
| | SUFFICIENT INFORMATION FOR REVIEW, CONSTRUCTION, AND |
| | INSPECTION. |
| | |
| | REVISE PLANS TO PROVIDE THE FOLLOWING: |
| | STEEL LAP SPECIFICATION |
| | MINIMUM EMBEDMENT OF STEEL TO BEAM ABOVE |
| | SPECIFICATION OF HOW STEEL IS TO BE EMBEDDED INTO |
| | EXISTING BEAM |
| | PLANS SHOW STEEL INTO THE BEAM ABOVE, BUT NO STEEL |
| | EXTENDING FROM THE NEW COLUMNS AND SILL INTO EXISTING |
| | IT IS NOT CLEAR WHETHER THE COLUMNS ARE FORMED AND |
| | POURED OR IF THEY ARE TO BE FILLED CELLS; REVISE TO |
| | SPECIFY |
| | CONCRETE (OR GROUT) NOT SPECIFIED |
| | THE DETAIL IS ON A SHEET LABELED "TANK, DISPENSER, & |
| | PIPING SITE PLAN." PLANS SHOULD BE CLEAR AS TO SCOPE |
| | AND NATURE OF PROPOSED IMPROVEMENT, FBC 107. |
| | LOCATION OF PROPOSED NEW OPENING IS SHOWN GRAPHICALLY |
| | ON THE PLANS BUT NOT SPECIFIED (DISTANCE FROM CORNER). |
| | |
| | 8. THE PRODUCT APPROVAL FOR THE WINDOW (AND MULLION, IF |
| | APPLICABLE) IS TO BE REVIEWED BY DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL, FBC 107. |
| | |
| | 9. AERIALS SHOW A RECTANGULAR OBJECT IN THE LOCATION OF |
| | THE PROPOSED NEW WINDOW OPENING. REVISE PLAN TO CLARIFY |
| | WHAT IS CURRENTLY IN THIS LOCATION (WINDOW? ELECTRIC |
| | METER?), FBC 107. |
| | |
| | 10. PROVIDE PLANS STAMPED BY FDEP, FAC62-761. |
| | |
| | 11. IT IS RECOMMENDED THAT A SEPARATE SUBMITTAL FOR |
| | EACH PERMIT IS PROVIDED. AS SUBMITTED, NO PORTION OF |
| | THE WORK CAN BE ISSUED UNTIL ALL ITEMS HAVE BEEN |
| | ADDRESSED. |
| | |
| | 12. PROVIDE PLANS FOR THE CANOPY. A PERMIT APPLICATION |
| | HAS BEEN SUBMITTED, BUT STRUCTURAL PLANS WERE NOT |
| | PROVIDED. IT IS RECOMMENDED THAT THIS BE A SEPARATE |
| | SUBMITTAL WHICH SHOULD INCLUDE THE SITE PLAN AND |
| | STRUCTURAL DETAILS, INCLUDING ELEVATIONS. |
| | |
| | 13. PROVIDE SPEC SHEETS FOR THE PROPOSED FUEL |
| | DISPENSERS. FUEL DISPENSERS ARE TO COMPLY WITH FBC A |
| | 228. SPEC SHEETS SHOULD SHOW COMPLIANCE. PROVIDE ENOUGH |
| | INFORMATION (FOR INSTANCE, CURB HEIGHT) TO SHOW |
| | COMPLIANCE. |
| | |
| | 14. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE |
| | TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR |
| | PERMIT ISSUANCE. |
| | |
| | OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED |
| | FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS |
| | SHOULD BE MARKED "VOID" OR "OLD SHEETS". |
| | |
| | THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY |
| | DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS |
| | THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS. |
| | |
| | A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED |
| | WILL HELP TO EXPEDITE YOUR PLAN REVIEW. |
| | |