| 2018-11-14 10:47:09 | 4TH REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | 1. SHT. P-3.0.07 THE GAS RISER DIAGRAM IS LABELED |
| | PRESSURE 2-4 FL SOUTH. PLEASE CLARIFY WPB AMEND TO FBC |
| | 107.2.1 |
| | 2. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE #304 THE |
| | BTU LOAD IS ILLEGIBLE. PLEASE CLARIFY WPB AMEND TO FBC |
| | 107.2.1 |
| | 3. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE # 2011, |
| | 2014 AND 1002 ARE NOT SHOWN ON THE RISER DIAGRAM. |
| | PLEASE CLARIFY WPB AMEND TO FBC 107.2.1 |
| | 4. BELOW THE EQUIPMENT SCHEDULE THERE IS A NOTE |
| | REFERENCING THE KITCHEN CONSULTANT?S DRAWINGS FOR |
| | EQUIPMENT LOCATION AND FINAL LOADS. FOR THE GAS RISER |
| | IT IS REQUIRED THAT THE CORRECT BTU LOAD BE INDICATED |
| | ON THE PLAN AND THEY SHALL MATCH THE KITCHEN |
| | CONSULTANTS DRAWINGS. PLEASE CLARIFY WPB AMEND TO FBC |
| | 107.2.1. |
| | 5. SHT. P-3.0.07 THE BTU LOAD ON THE RISER FOR THE |
| | BANQUET KITCHEN DETAIL #D DOES NOT MATCH THE TOTAL FROM |
| | WHEN I ADDED UP THE EQUIPMENT SCHEDULE. PLEASE CLARIFY |
| | WPB AMEND TO FBC 107.2.1. |
| | 6. SHT. P-3.0.07 THE BTU LOAD ON THE A BRANCH OFF THE |
| | MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED |
| | ISOMETRIC #A . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| | 7. SHT. P-3.0.07 THE BTU LOAD ON THE C BRANCH OFF THE |
| | MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED |
| | ISOMETRIC #C . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| | 8. SHT. P-3.0.07 WHEN I TOTALED UP THE BTU LOADS FROM |
| | THE EQUIPMENT SCHEDULE IT WAS 4,783,000 THE TOTAL GAS |
| | LOAD UNDER THE 1ST STAGE GAS LOAD CALCULATION WAS |
| | 4,624,000 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| | |
| | PREVIOUS COMMENTS 2. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE FBC-2014 |
| | FUEL GAS CODE SEC. 304. PLEASE PROVIDE COMBUSTION AIR |
| | CALC FOR |
| | THE KITCHEN APPLIANCES. |
| | RESPONSE: GAS WATER HEATER IS DIRECT VENT/INTAKE. |
| | PLEASE CONFIRM REQUIREMENT OF CALCULATION. |
| | PLEASE REFER TO KITCHEN CONSULTANT FOR KITCHEN |
| | EQUIPMENT INFORMATION. |
| | THIS RESPONSE DOES NOT COMPLY PLEASE PROVIDE COMBUSTION |
| | AIR CALCULATIONS FOR THE KITCHENS THEY SHALL BE |
| | INCLUDED IN THE GAS OR MECHANICAL PLANS. |
| | |
| | PREVIOUS COMMENT 4. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA |
| | 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED THESE TO |
| | VERIFY BTU |
| | LOADS-IF THEY CAN NOT BE PROVIDED FOR PLAN REVIEW PLACE |
| | A |
| | NOTE ON THE PLAN TO BE ON JOBSITE FOR FIRST ROUGH |
| | INSPECTION. |
| | RESPONSE: PLEASE REFER TO KITCHEN EQUIPMENT CONSULTANT |
| | PLANS FOR REFERENCE. |
| | THE RESPONSE DOES NOT COMPLY THE KITCHEN CONSULTANTS |
| | PLANS ARE NOT INCLUDED IN SUBMITTAL AND WE REQUIRE THE |
| | SPECIFICATION FROM THE APPLIANCE MANUFACTURE NOT THE |
| | CONSULTANT. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |