| Date |
Text |
| 2018-09-07 11:32:54 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17020796 |
| | 9/7/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE MATCH THE GUEST ROOM FC SYSTEM |
| | IDENTIFICATIONS ON THE AC AND ENERGY CALCULATIONS, AND |
| | THE SCHEDULE ON SHEET M-0.0.02. EACH DOCUMENT |
| | IDENTIFIES THEM DIFFERENTLY WHICH MAKES OT DIFFICULT TO |
| | REVIEW FOR COMPLIANCE. IT APPEARS THAT MANY OF THE |
| | SYSTEMS AS THEY ARE SHOWN IN THE CALCULATIONS ARE BEING |
| | GROUPED TOGETHER BUT THERE IS NO EXPALNATION OF HOW |
| | THEY ARE BEING GROUPED- PLEASE CLARIFY. |
| | |
| | 2) THE PREVIOUSLY REQUESTED COMBUSTION AIR CALCULATIONS |
| | FOR THE GAS-FIRED COOKING APPLIANCES WERE NOT PROVIDED. |
| | |
| | 3) SHEET M-1.3.01B: THE VENTILATION CA;LCULATION FOR |
| | THE WOMEN'S LOCKER ROOM IS INCORRECTLY LISTED AT 170 |
| | CFMS , HOWEVER 204 CFMS ARE REQUIRED. |
| | |
| | 4) M-1.3.01B & M-1.4.01: IT APPEARS THAT RECIRCULATION |
| | OF THE AIR FROM THE MANI/PEDI ROOM IS BEING |
| | RECIRCULATED TO OTHER ROOMS AND SPACES VIA THE RETURN |
| | TRANSFER FROM THE ROOM INTO THE PLENUM WHICH IS |
| | PROHIBITED PER TABLE 403.3 FOOTNOTE B. |
| | |
| | 5) M-1.3.01B & M-1.4.01: THE MANI/PEDI PLAN DOES NOT |
| | INDICATE THAT SOURCE CAPTURE SYSTEMS ARE TO BE |
| | INSTALLED AT EACH MANICURE TABLE AND PEDICURE CHAIR- |
| | TABLE 403.3 FOOTNOTE |
| | |
| | 6) M-1.3.01B: VENTILATION IS REQUIRED FOR THE FIRE PUMP |
| | ROOM- SECTIONS 4.12.6 & 11.3.2.1 NFPA 20. |
| | |
| | 7) M-1.3.01B: FIRE DAMPERS MISSING AT: A) 20X14 SUPPLY |
| | DUCT PENETRATING THE BOH CORRIDOR WALL. B) THE 30X14 |
| | SUPPLY AND RETURN DUCTS PENETRATING MECH RM 1205 WALLS- |
| | SECTION 607.5.2. |
| | |
| | 8) PROVIDE AN AC CONDENSATE PIPING PLAN AND RISER |
| | DRAWING- SECTION 307. |
| | |
| | 9) PROVIDE UL APPROVED FIRESTOPPING SYSTEMS FOR THE |
| | CHILLED WATER PIPING AND CONDENSATE PIPING. |
| | |
| | 10) REFER TO SECTION 3004.1 FBC-14 BUILDING AND |
| | INDICATE HOW THE ELEVATOR HOISTWAYS ARE BEING VENTED. |
| | |
| | 11) REFER TO SECTIONS C408.1 & C408.2 FBC-14 ENERGY |
| | CONSERVATION: COMMISSIONING OF THE MECHANICAL AND |
| | ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED. |
| | |
| | C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION |
| | REQUIREMENTS. |
| | PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE |
| | REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE |
| | OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN |
| | ACCORDANCE THE PROVISIONS OF THIS SECTION. |
| | |
| | CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE |
| | PROVISIONS FOR COMMISSIONING AND COMPLETION |
| | REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE |
| | PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER |
| | REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE |
| | GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE |
| | OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS |
| | C408.2.4 AND C408.2.5. |
| | |
| | |
| | ADVISORIES: |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, WALKIN |
| | COOLERS AND FREEZERS, FIRE ALARM, FIRE SPRINKLER. |
| | |
| | 2) INCLUDED WIH THE KITCHEN EXHAUST HOOD DRAWINGS SHALL |
| | BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR AND |
| | EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL COMPONENTS |
| | WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE. B) |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C) |
| | CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST |
| | TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED |
| | CLEARANCES TO PARTS OF THE BUILDING- SECTION |
| | 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE |
| | MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR |
| | TEMPERATURE IN THE KITCHEN- SECTION 508.1.1. |
| | |
| | 3) DEFERRED SUBMITTALS: |
| | |
| | A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE |
| | CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL |
| | EQUIPMENT. |
| | B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE |
| | EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING |
| | MANUFACTURER'S SPECIFICATIONS. |
| | C) FIRE DAMPERS |
| | D) MOTORIZED DAMPERS. |
| | E) DUCT SMOKE DETECTORS. |
| | F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE |
| | INSULATIONS. |
| | G) FLAMEBAR DUCT INSTALLATION DETAILS. |
| | H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER |
| | FROM BUILDING OWNERSHIP. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |