| 2018-09-11 12:35:15 | 3ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | GAS COMMENTS: PREVIOUS COMMENTS |
| | |
| | PARTIALLY COMPLIED 1. 1. SUBMIT AN ISOMETRIC DRAWING |
| | THAT CLEARLY SHOWS ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. AND BTU LOAD OF EACH APPLIANCE. ALSO |
| | SHOW ALL VALVE DRIP LEGS AND REGULATORS REFER TO THE |
| | FBC-2014 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES |
| | 402.4(1) THRU 402.4(37). |
| | PLEASE PROVIDE THE LENGTH OF EACH CUT SECTION OF PIPE. |
| | PLEASE SHOW BTU LOAD FOR EACH GAS APPLIANCE.THE NUMBERS |
| | ON THE ENLARGE BANQUET KITCHEN ISO DO NOT ALL MATCH THE |
| | GAS EQUIPMENT SCHEDULE. |
| | |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. PLEASE PROVIDE |
| | COMBUSTION AIR CALC FOR THE KITCHEN APPLIANCES. |
| | |
| | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| | SEC. 502 THRU 505. IN YOUR RESPONSE YOU NOTE VENT |
| | DETAILS ON SHT P-3.0.08 I COULD NOT LOCATE ANY VENT |
| | DETAILS ON THAT SHT PLEASE CLARIFY. |
| | |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED |
| | THESE TO VERIFY BTU LOADS-IF THEY CAN NOT BE PROVIDED |
| | FOR PLAN REVIEW PLACE A NOTE ON THE PLAN TO BE ON |
| | JOBSITE FOR FIRST ROUGH INSPECTION. |
| | |
| | 2ND REVIEW COMMENTS: NOT COMPLIED |
| | |
| | 1. SHT. P-3.0.08 ON THE GAS ISOMETRIC THE 2ND BRANCH |
| | UPSTREAM OF THE METER HAS IS LABELED AS MAIN KITCHEN |
| | SHT. P-1.5.07 WHICH LABELS IT AS THE BANQUET KITCHEN |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. WHAT IS THE 3/4" BRANCH WITH THE NOTE FIX TAG PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. WHAT IS THE 2" AT THE UPSTREAM END OF THE ISOMETRIC |
| | WITH THE TAG XXXMBH/L.F.=XX' PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 6. ON THE ENLARGED ISOMETRIC DRAWING PLEASE SHOW THE |
| | PRESSURE REGULATORS AND THE VALVES ALSO SHOW THE LENGTH |
| | AND SIZE OF THE PIPING BETWEEN THE REGULATOR AND THE |
| | APPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. PLEASE LABEL THE ENDS OF THE PIPE WHERE THEY |
| | CONTINUES. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT |
| | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |