| 2018-05-08 12:31:12 | 2ND REVIEW |
| | FBC 2014 5TH EDITION |
| | PERMIT# 17020796 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | !!!! IN ORDER TO TO EXPIDITE AN APPROVAL FOR THIS |
| | PERMIT I SUGEST A MEETING BE SCHDULED TO GO OVER THE |
| | PLAN PLEASE CONNTACT ME @ 561-805-6711 !!! |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED SEE |
| | NEW COMMENTS |
| | |
| | 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER |
| | FBC PL 704. |
| | |
| | 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE |
| | FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR |
| | EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. ALL THE ACCESSIBILITY SHALL COMPLY WITH FLORIDA |
| | BUILDING CODE ACCESSIBILITY 2014 5TH EDITION PLEASE |
| | NOTE ON THE PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. P-3.0.05 THE 1" HOT WATER RECIRCULATION LINE |
| | DOES NOT SHOW UP ON THIS SHEET PLEASE CLARIFY. PER FBC |
| | PL 607.2 |
| | |
| | 3. SHT. P- 1.5.10 THE SANITARY PIPING DID NOT SHOW UP |
| | ON THIS SHEET PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. SHT. P-3.0.00 AND P-3.0.02 PLEASE SHOW THE SIZE AND |
| | SLOPE ON THE ISOMETRIC WE NEED THIS TO CHECK SIZING THE |
| | TABLE THAT WAS PROVIDED DOES NOT SPECIFY THE SLOPE IT |
| | ONLY GIVES A MINIMUM THE SIZING TABLE FBC PL TABLE |
| | 710.1(1) USES SPECIFIC SLOPE TO SIZE THE PIPE. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. P-1.1.00 THE SOUTH GREASE INTERCEPTOR DID NOT |
| | SHOW UP ON THE SHEET IT IS ALSO MISSING THE GREASE AND |
| | SANITARY PIPING PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. SHT. P-3.0.02 TWOWAY CLEANOUTS ARE REQUIRED BETWEEN |
| | EACH INTERCEPTOR PLEASE SHOW ON PLAN. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 7. ON THE SANITARY ISOMETRIC DRAWINGS GOING FROM THE |
| | FIRST FLOOR TO THE 2ND, 3RD, AND 4TH FLOOR SOME OF THE |
| | ID TAGS ARE NOT MATCHING UP SOME ARE MISSING AND ON THE |
| | DRAWING FOR THE UPPER FLOOR IT APPEARS THE BRANCHES ARE |
| | MISSING THESE ISOMETRIC DRAWING ARE TO CONFUSING TO |
| | DETERMINE CODE COMPLIANCE PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 8. THE FLOOR PLANS ARE MISSING THE ID TAGS TO MATCH UP |
| | THE SANITARY STACKS TO THE ISOMETRIC DRAWINGS PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. IN YOUR RESPONSE TO COMMENT #21 YOU REFER TO DETAIL |
| | ON SHT. P-4.0.04 THIS SHEET IS MISSING FROM THIS |
| | SUBMITTAL PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHT. P- 1.4.07 PLEASE REMOVE THE GAS ISOMETRIC FROM |
| | THE WATER ISO IT SHOULD BE ON SHT. P-3.0.08 AND LABEL |
| | ALL FIXTURE SOME ARE MISSING LABELS. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 11. SHT. P-3.0.07 PLEASE LABEL ALL THE FIXTURES AND |
| | BRANCHES FOR THE UNITS ALSO SHOW THE SIZE ON ALL THE |
| | PIPING. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |