| Date |
Text |
| 2017-04-21 11:15:07 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A1.9.01 PLEASE SHOW CLEAR FLOOR SPACE FOR |
| | ACCESSIBLE URINAL COMPLYING WITH FBC ACC 605.3 |
| | 2. PLEASE SHOW COMPLIANCE FOR SEATS, CONTROLS, GRAB |
| | BARS, CLEAR FLOOR SPACE, SIZES PER FBC ACC 607 TUBS AND |
| | 608 SHOWERS. |
| | 3. PROVIDE ELEVATIONS AND CLEAR FLOOR SPACE FOR |
| | ACCESSIBLE GUEST BATHROOMS. PER FBC ACC 806.2.4 |
| | 4. SHT. A-1.5.02 DETAILS 3 AND 4 GUESTROOM DOUBLE 6 AND |
| | 7 SHOW THE SAME ROOM NUMBERS PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 5. PLEASE PROVIDE ENLARGED FLOW PLANS FOR ACCESSIBLE, |
| | KING W/SHOWER RM # 3315 AND DOUBLE W/SHOWER RM# 3313 |
| | PLEASE INCLUDE DIMENSIONS FOR SHOWER. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 6. SHT. A-1.5.02 DETAIL 3 DOUBLE 6 THE LAVATORY TOP IS |
| | ENCROACHING INTO THE 60? CLEAR FLOOR SPACE OF TOILET. |
| | PER FBC PL 604.3.1 |
| | 7. SHT. P-4.0.01 FOR THE FIRE ASSEMBLY?S, PROVIDE |
| | MANUFACTURE AND STANDARD THEY MEET SUCH AS UL. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 8. PROVIDE TYP. WATER RISER FOR GUEST UNIT BATHROOMS. |
| | PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 9. A CLEAN OUT IS REQUIRED AT THE BASE OF EACH SOIL OR |
| | WASTE STACK. PER FBC PL708.3.4 |
| | 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER |
| | FBC PL 704. |
| | 11. PROVIDE DFU LOAD ON STACKS AND BUILDING DRAIN. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE |
| | FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 13. SHT. P-4.0.00 DETAIL # 2 SHOWS DRAIN FROM SUMP PUMP |
| | DRAINING TO THE STORM DRAIN IT IS ALSO SHOWN DUMPING |
| | INTO SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 14. SHT. P-1.1.00 THE GREASE TRAP CALCULATION THAT WERE |
| | USED ARE FOR ESTABLISHMENTS WITH COMMERCIAL KITCHENS |
| | THIS APPLICATION SHALL BE FOR RESTAURANTS IT?S A |
| | DIFFERENT CALCULATION USING NUMBER OF SEATS AND HOURS |
| | OF OPERATION. PER FBC PL 1003.2 |
| | 15. LABEL ALL FIXTURES ON RISER DIAGRAMS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 16. P-3.0.02 THE BRANCH DRAIN FOR THE FLOOR DRAIN AND |
| | LAVS IN MEN?S BATHROOM #1149 SHALL NOT ROLL UP OVER THE |
| | 8" BUILDING DRAIN YOU CAN ROLL THE BRANCH DRAIN FOR THE |
| | WHOLE GAIN BATHROOM UP TO CLEAR THE BUILDING DRAIN MAIN |
| | TRUNK LINE. PER FBC PL 901.2.1 |
| | 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 18. PLEASE PROVIDE KITCHEN EQUIPMENT PLAN AND SCHEDULE |
| | FOR #1129, #1118 AND #1119. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 19. PROVIDE PLUMBING FLOOR PLAN WITH THE SOIL STACKS |
| | LABELED TO MATCH RISER DIAGRAM. FOR FIRST FLOOR. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 20. HORIZONTAL DRY VENTS ARE PROHIBITED BELOW FLOOD |
| | LEVEL RIM OF FIXTURES I FOUND A FEW IN THE KITCHEN, |
| | RETAIL COFFEE AND THE BAR ALSO IN THE COUPLE?S SUITE ON |
| | THE TUB DRAIN. PER FBC PL 905.3/ 905.4 |
| | 21. PROVIDE TRAP PRIMERS ON ALL FLOOR DRAINS. PER FBC |
| | PL 1002.4 |
| | 22. SHT. P-1.3.01B AND P-1.4.01B SHOWS A SINGLE |
| | DRINKING FOUNTAIN IN FITNESS AREA, TWO DRINKING |
| | FOUNTAINS ARE REQUIRED. PER FBC ACC 211.2 |
| | 23. SHT. P-1.4.01B AND P-3.0.06 WATER PIPING FOR |
| | DRINKING FOUNTAIN IN FITNESS AREA IS NOT SHOWN PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR |
| | EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 25. SHT. P-3.0.07 SHOWS UNITS 3309 AND 3314 PROVIDE |
| | RISER FOR 4TH FLOOR WITH THESE UNITS REMOVED. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 26. PROVIDE WATER RISERS FOR BOTH KITCHENS, BAR, RETAIL |
| | COFFEE AND SERVICE PER WPB AMEND TO FBC 107.2.1EA. |
| | 27. SHT. P-4.0.00 THE GAS WATER HEATER DETAIL DOES NOT |
| | MATCH THE RISER ON SHT. P3.0.07 PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 28. SHT. P-4.0.00 THE GAS WATER HEATER DETAIL SHOWS A |
| | 110 DEG. AND 140 DEG. PIPE BUT THE RISER DOES NOT A MIN |
| | OF 110 DEG IS REQUIRED IN THE KITCHENS HOW WILL THIS BE |
| | ACCOMPLISHED PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 29. SHT. P.3.0.02 THE RISER IS MISSING THE DRAIN FOR |
| | THE ACCESSIBLE SHOWERS IN THE MEN?S AND WOMEN?S LOCKER |
| | ROOM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 30. PROVIDE THE DIMENSION FOR ALL SHOWERS IN THE LOCKER |
| | ROOMS. PER WPB AMEND TO FBC 107.2.1 |
| | 31. ALL PLAN SHEETS SHALL BE DIGITALLY SIGNED BY THE |
| | DESIGN PROFESSIONAL RESPONSIBLE FOR DRAWING. PER FAC |
| | 61G1-16.005 |
| | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT |
| | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |