| 2017-04-05 12:58:38 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17020796 |
| | 4/3/17 |
| | |
| | 1) THE UPLOADED DIGITAL MECHANICAL PLANS, ENERGY AND AC |
| | CALCULATIONS REQUIRE ELECTRONIC SEALS AND SIGNATURES BY |
| | THE ENGINEER OF RECORD IN ACCORDANCE WITH SECTION |
| | 471.025 FLORIDA STATUTES, AND SECTION 61G15-23.005 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED |
| | FOR THE KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION |
| | SYSTEMS, AND THE WALK-IN COOLERS AND FREEZERS. |
| | REGARDING THE KITCHEN HOODS PLEASE SEE SECTION 508.1.1 |
| | FBC-14 MECHANICAL- MAKEUP AIR TEMPERATURE. THE CURRENT |
| | PLAN IS NOT IN COMPLIANCE. |
| | |
| | 3) THE AC COOLING AND HEATING CALCULATIONS ARE |
| | INCORRECTLY SPECIFYING MIAMI AS THE LOCATION AND ORIGIN |
| | OF DESIGN DATA FOR THE PROJECT. |
| | |
| | 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | GUEST ROOMS AND ALL OTHER HABITABLE ROOMS SERVED BY THE |
| | FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 5) REGARDING THE UPLOADED AC CALCULATIONS PLEASE NOTE |
| | THE TOTAL COOLING CAPACITIES FOR AHU?S 3 & 5 SHOWN IN |
| | THE SCHEDULE ON SHEET M-0.0.02- (68.6 & 63.3 MBH) DO |
| | NOT MATCH THE CALCULATED LOADS OF (169.3 & 127 MBH). |
| | |
| | 6) REFER TO TABLE C403.2.3(7) FBC-14 ENERGY |
| | CONSERVATION: IT APPEARS THE EFFICIENCY CRITERIA FOR |
| | THE CHILLER SHOWN ON THE ENERGYGAUGE COMPLIANCE |
| | SUBMITTAL IS INCORRECT FOR AN AIR-COOLED CHILLER. |
| | |
| | 7) SHEET M-0.0.0.1: PLEASE UPDATE THE SMACNA SECOND |
| | EDITION REFERENCE AND PROVIDE DUCT HANGER TABLES IN |
| | COMPLIANCE WITH THE 2005 THIRD EDITION. |
| | |
| | 8) SHEET M-0.0.03: PLEASE UPDATE THE ASHRAE 62.1-2004 |
| | REFERENCE AND PROVIDE VENTILATION RATES IN ACCORDANCE |
| | WITH THE CURRENT 2010 STANDARD IN EFFECT. PLEASE SEE |
| | TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3 FBC-14 |
| | MECHANICAL AND PROVIDE THE VENTILATION RATES FOR THE |
| | GUESTROOMS. |
| | |
| | 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR |
| | HANDLERS AND FAN COIL UNITS- SECTION 307. |
| | |
| | 10) PROVIDE ENLARGED KITCHEN AND FOOD SERVICE DRAWINGS. |
| | |
| | 11) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO |
| | THE GAS-FIRE COOKING APPLIANCES AND WATER HEATERS AND |
| | PROVIDE CALCULATIONS- REFER TO SECTION 304 FBC-14 FUEL |
| | GAS. PROVIDE WATER HEATER VENTING DIAGRAMS THAT |
| | INDICATE THE TYPE AND SIZE OF THE VENTS, TOTAL VENT |
| | RUNS AND TERMINATION LOCATIONS. |
| | |
| | 12) M-1.3.01A: LABEL THE EXHAUST RISER LOCATIONS FOR |
| | KEF-4 & 5. |
| | |
| | 13) M-1.3.01A: MISSING FIRE DAMPERS- A) 8X8 DUCT |
| | PENETRATING THE UNISEX RESTROOM/BOARDROOM #1 WALL. B) |
| | 30X14 DUCT AT CORRIDOR 1110/BANQUET PANTRY WALL. |
| | |
| | 14) M-1.3.01A & B: PROVIDE THE FLEX DUCT SIZES ON THE |
| | PLAN. |
| | |
| | 15) M-1.3.01A & B: SHOW THE LOCATIONS OF ALL REQUIRED |
| | ACCESS PANELS FOR ALL FAN COIL UNITS AND VAV BOXES |
| | LOCATED ABOVE HARD CEILINGS- SECTION 306.1. |
| | |
| | 16) M-1.3.01A & B: PROVIDE DUCT SMOKE DETECTORS IN THE |
| | RETURN AIR SYSTEMS OF THE AHU'S- SECTION 606.2.1. |
| | |
| | 17) M-1.3.01A & B: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR THE KITCHENS, THE TOILET AND |
| | BATHROOMS, THE LOCKER ROOMS, AND THE MANICURE/PEDICURE |
| | SPA- SEE TABLE 403.3. PROVIDE ENLARGED DRAWINGS OF THE |
| | EXHAUST SYSTEMS THAT INDICATE THE TYPES AND SIZES OF |
| | EXHAUST DUCTS, TOTAL EXHSAUST VENT RUNS, AND INLET AND |
| | OUTLET LOCATIONS- SEE TABLE 403.3 FOOTNOTE B AND H. |
| | |
| | 18) M-1.3.01A & B: PROVIDE AIR BALANCE CALCULATIONS. |
| | |
| | 19) M-1.3.01A & B: DEMAND CONTROLLED VENTILATION IS |
| | REQUIRED FOR THE DINING/LOUNGE, FITNESS, AND BALLROOMS |
| | 1 & 2- REFER TO SECTION C403.2.5.1 AND PROVIDE A MEANS |
| | OF COMPLIANCE ON THE PLAN. |
| | |
| | 20) M-1.3.01A & B: THE LOCATIONS AND REQUIRED CLEARANCE |
| | DISTANCES FOR O/A INTAKES AND EXHAUST OUTLETS SHALL BE |
| | IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1. PLEASE |
| | PLACE NOTES OR SHOW CLEARANCE DISTANCE MEASUREMENTS ON |
| | THE PLAN TO VERIFY COMPLIANCE. |
| | |
| | 21) M-1.3.01A: CLARIFY HOW O/A IS BEING PROVIDED TO |
| | AHU-5. IT APPEARS THE INLET AT MECHANICAL 11120 IS |
| | LABELED MAKEUP AIR. |
| | |
| | 22) M-1.3.01B: MISSING FIRE DAMPERS FOR DUCTS |
| | PENETRATING A) CORRIDOR 1135/SECURITY-RECEIVING WALL. |
| | B) DUCT PENETRATING THE CORRIDOR 1157/F.O. ADMIN WALL. |
| | |
| | 23) M-1.3.01B: LABEL THE O/A INLET FOR AHU-3. |
| | |
| | 24) M-1.3.01C: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| | UNDERGROUND CHILLED WATER PIPING RUNS FROM THE CHILLER |
| | AND PUMPS ETC. INTO THE BUILDING. INDICATE THE TYPE AND |
| | SIZE OF PIPING, TYPE AND THICKNESS OF INSULATION. |
| | |
| | 25) M-1.3.01C: WIND LOAD ENGINEERING IS REQUIRED FOR |
| | ANCHORING THE CHILLER, THE PUMPS, AIR SEPARATOR, |
| | EXPANSION TANK, AND THE CHILLED WATER PIPING- SEE |
| | SECTION 301.15 . PLEASE SEE SECTION 1609 FBC-14 |
| | BUILDING AND PROVIDE DETAILS AND DESIGN CRITERIA. |
| | |
| | 26) M-1.3.02A, 2B, 3A, 3B, 4A, 4B: LABEL THE O/A |
| | INTAKES FOR THE FC UNITS, AND PROVIDE AUTOMATIC SHUTOFF |
| | DAMPERS FOR THE O/A DUCTS- SECTION C403.2.4.4 FBC-14 |
| | ENERGY CONSERVATION. |
| | |
| | 27) M-1.5.02, 03, 04, 05: PROVIDE RETURN AIR FOR THE FC |
| | UNITS IN THE GUESTROOMS, AND PROVIDE AN ENLARGED DETAIL |
| | SHOWING HOW ACCESS WILL BE PROVIDED FOR MAINTENANCE AND |
| | REPLACEMENT OF THE UNITS- SECTION 306.1. |
| | |
| | 28) M-3.0.00: PROVIDE EITHER NOTES OR DETAILS ON THE |
| | RISER PLAN INDICATING THE TYPE OF O/A DUCTWORK, |
| | LOCATIONS OF FIRE DAMPERS ETC. |
| | |
| | 29) PLEASE PROVIDE TOILET EXHAUST RISER DRAWINGS |
| | INCLUDING THE TYPES AND SIZES OF EXHAUST DUCTS, |
| | VERTICAL RUN LENGTHS OF SUB-DUCTS, AND EXHAUST CFMS. |
| | |
| | 30) M-1.3.04A, 4B, 5A & 5B: PROVIDE WIND LOAD |
| | ENGINEERING FOR TIE-DOWN OF THE ROOFTOP DUCTWORK, THE |
| | TOILET EXHAUST OUTLETS, AND THE O/A INTAKE HOODS. |
| | PLEASE NOTE THAT FLORIDA PRODUCT APPROVALS AND/OR |
| | MIAMI-DADE NOA'S ARE REQUIRED FOR ANY MANUFACTURED |
| | EXTERIOR MECHANICAL EQUIPMENT SUPPORTS OR STANDS. |
| | |
| | 31) M-1.3.05A, 5B: IT APPEARS THAT FLAMEBAR DUCTWORK IS |
| | MISSPELLED AS BAMEBAR- PLEASE CORRECT. |
| | |
| | 32) M-1.3.04B: THE LOCATION OF THE EXHAUST OUTLETS FOR |
| | KEF- 1, 2 & 3 APPEAR TO BE NON-COMPLIANT WITH SECTION |
| | 506.13.3 WHICH REQUIRES A 10' HORIZONTAL CLEARANCE |
| | DISTANCE FROM THE OUTLETS TO PARTS OF THE SAME OR |
| | CONTIGUOUS BUILDING. PLEASE SEE THE EXCEPTION UNDER |
| | THIS SECTION FOR FURTHER INFORMATION. |
| | |
| | 33) M-1.3.05A: THE LOCATIONS OF THE EXHAUST OUTLETS FOR |
| | KEF-4 & 5 APPEAR TO BE NON-COMPLIANT WITH SECTIONS |
| | 506.3.13.1 & 506.3.13.3. PLEASE PROVIDE CLEARANCE |
| | DISTANCE MEASUREMENTS. PLEASE NOTE THAT ADDITIONAL |
| | COMMENTS REGARDING THE KITCHEN COOKING EXHAUST SYSTEMS |
| | MAY OCCUR AFTER COMPLETE PLANS AND SPECIFICATIONS ARE |
| | SUBMITTED FOR REVIEW UNDER SEPARATE PERMIT. |
| | |
| | 34) INDICATE HOW ACCESS IS BEING PROVIDED FOR |
| | SERVICEABLE MECHANICAL EQUIPMENT LOCATED ON THE |
| | BUILDING ROOFTOPS (I.E. EF-4-1, EF-5-1, KEF-4 & 5)- |
| | SECTION 306.5. ADDITIONALLY PLEASE NOTE THAT ACCESS |
| | SHALL NOT REQUIRE WALKING ON ROOFS WITH A SLOPE GREATER |
| | THAN 4 UNITS VERTICAL IN 12 HORIZONTAL. |
| | |
| | 35) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE |
| | NOA'S FOR THE O/A INTAKE AND EXHAUST OUTLET LOUVERS. |
| | |
| | 36) PROVIDE APPROVED PRODUCT SUBMITTAL DOCUMENTS FOR |
| | THE FLAMEBAR DUCT, THE MOTORIZED DAMPERS, AND THE CO2 |
| | SENSORS. |
| | |