| 2017-04-11 09:18:36 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW |
| | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ELEVATORS, KITCHEN HOOD SYSTEMS, ETC. |
| | A NOTE WILL SUFFICE. |
| | 2. SHEET E0.0.02- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| | INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| | SUFFICE |
| | 3. SHEET E0.0.02- ADD A NOTE TO MAINTAIN ALL ELECTRICAL |
| | EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE |
| | AND CITY REGULATORY AGENCIES. |
| | 4. SHEET E0.0.02- PLEASE CORRECT ALL CODES APPLICABLE |
| | REFERENCES TO REFLECT ABOVE STATED. DELETE BROWARD AND |
| | INTERNATIONAL CODES. ADD WPB AMENDMENTS. |
| | 5. NOTE THAT PLANS ARE NOT DIGITALLY SIGNED AND SEALED. |
| | FBC 107.3.5 |
| | 6. E1.3.01B- PLEASE PROVIDE EM LIGHTING FOR MAIN |
| | ELECTRICAL ROOM AND ELECTRICAL ROOMS. FBC 107.3.5 |
| | 7. ALL BALCONIES MUST HAVE A RECEPTACLE OUTLET, SEE ALL |
| | UNITS. NEC 210.52E3. |
| | 8. PROVIDE A NOTE TO COMPLY WITH NEC 210.5- |
| | IDENTIFICATION FOR BRANCH CIRCUITS- A- GROUNDED |
| | CONDUCTOR PER NEC 200.6 AND UNGROUNDED CONDUCTORS PER |
| | NEC 210.5C1,2,3- APPLICATION, MEANS OF IDENTIFICATION |
| | AND POSTING OF IDENTIFICATION MEANS. |
| | 9. PROVIDE A NOTE ON UNIT SHEETS TO INDICATE TAMPER |
| | RESISTANT RECEPTACLE REQUIRED PER NEC 406.13 |
| | 10. SHOW A MASTER SWITCH FOR ALL UNITS AT THE ENTRY PER |
| | FBC EC405.2.3 LIGHTING AND SWITCHED RECEPTACLE. SHOW |
| | COMPLIANCE. |
| | 11. SHEET E-2.2.00- PROVIDE A NOTE INDICATING GFCI |
| | PROTECTION REQUIRED WITHIN 6FT OF EVERY SINK PER NEC |
| | 210.8B5, AND FOOD PREPARATION ADJACENT AREAS. |
| | 12. RISER DIAGRAM AND PANEL SCHEDULES SHEETS. PLEASE |
| | PROVIDE AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL |
| | SERVICE. ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER |
| | & LIGHT INDICATING AIC. SHOW AIC CALCULATION BASED ON |
| | INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC |
| | 110.24 FBC 107.3.5 |
| | 13. AIC RATINGS REQUIRED TO BE SHOWN ON ALL |
| | PANELBOARDS. FBC 107.3.5 |
| | 14. PROVIDE ACTUAL VOLTAGE DROP CALCULATIONS NOT ONLY |
| | FOR FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 |
| | 15. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC |
| | 110.26C3, REQUIRES PERSONNEL DOORS TO BE EQUIPPED WITH |
| | PANIC HARDWARE AND OPEN IN THE DIRECTION OF EGRESS. A |
| | NOTE WILL SUFFICE. |
| | 16. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM |
| | TO INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 17. PLEASE CLARIFY FIRE PUMP SHOWN ON RISER DIAGRAM FOR |
| | A COMPLETE REVIEW. COULD NOT LOCATE WHERE IT IS |
| | LOCATED, AND LOCATION OF ATS/FP CONTROLLER. FBC 107.3.5 |
| | 18. PROVIDE INFORMATION ON DRAWINGS AND DATA SHEETS FOR |
| | LIGHTING CONTROL PANELS. CLARIFY COMPLIANCE WITH FBC |
| | ENERGY CONSERVATION. |
| | 19. CLARIFY AS NO ELEVATOR MACHINE ROOMS ARE SHOWN TO |
| | COMPLY WITH NEC 620.23 A,B AND C. |
| | 20. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO |
| | ELECTRICAL.ADDITIONAL EXIT LIGHTS AND EM. PHOTOMETRICS |
| | FOR MINIMUM EGRESS LIGHTING LEVELS TO BE |
| | MAINTAINED.SHOW ADDITIONAL ELECTRICAL DEMAND FOR DUCT |
| | DETECTORS AND DAMPERS MISSING AND ROOFTOP ELECTRICAL |
| | RECEPTACLES FOR SERVICE OF EQUIPMENT IN AREA. NEC |
| | 210.63, FBC 107.3.5 |
| | 21. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |