| Plan Review Notes For Permit 17020767 |
| Permit Number |
17020767 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-07 13:59:57 | 17020767 | | | | | | 1) ROOM 100 FOYER | | | A) OUTLETS PER FBC RESIDENTIAL E3901.11 | | | B) SMOKE ALARM AT BOTTOM OF THE STAIRS NFPA 72 | | | 29.5.1.1.#3 | | | | | | 2) ROOM 103 SUN ROOM | | | A) OUTLET SPACING FBC RESIDENTIAL E3901.2 | | | | | | 3) ROOM 106 KITCHEN | | | A) SMOKE/ CO2 ALARM TO CLOSE TO STOVE NFPA 72 29.8.3.4 | | | (4) | | | B) OUTLET SPACING ON COUNTER BY SINK FBC RESIDENTIAL | | | E3901.4.1 | | | | | | 4) ROOM 113 COTTAGE AND MAIN HOUSE | | | A) FRONT OUTLETS MISSING ON BOTH FBC RESIDENTIAL | | | E3901.7 | | | | | | 5) AIR HANDLER ROOM IN BASEMENT | | | A) OUTLET MISSING FOR SERVICING THE UNIT FBC | | | RESIDENTIAL E3901.12 | | | | | | 6) ROOM 203 MASTER BEDROOM | | | A) OUTLETS BY BALCONY DOORS 6' FROM OPENING PER FBC | | | RESIDENTIAL E3901.1.2.4 | | | B) OUTLET ON BALCONY PER FBC RESIDENTIAL E3901.7 | | | | | | 7) ROOM 202 BATHROOM | | | A) PENDANT FIXTURE TO CLOSE TO TUB 410.10 (D) | | | | | | 8) ALL HAYWAYS UPSTAIRS | | | A) SMOKE ALARMS REQUIRED OUTSIDE OF BEDROOMS | | | B) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF ALL | | | BEDROOMS | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | WEST PALM BEACH, FL | | | |
|