| Plan Review Notes For Permit 17020767 |
| Permit Number |
17020767 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-27 15:24:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE STRUCTURAL DETAILS FOR THE INTEGRATED LADDER | | | TO THE BASEMENT MECHANICAL ROOM. FBC 107.2.1 & | | | FBC-R301.5 | | | | | | 2) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE VULKEM 350NF-R | | | WATERPROOFING. FBC-R406.2 | | | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL | | | MULLIONS AND EXTERIOR DOOR TYPES. | | | | | | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THE ROOF HATCH TO THE MECHANICAL ROOM THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. FAC 61G20-3.001 | | | | | | 5) SUBMIT TWO SETS OF THE PRODUCT EVALUATIONS FOR THE | | | ICYNENE SPRAY FOAM INSULATION. FBC-R316 |
|