Plan Review Notes
Plan Review Notes For Permit 17020757
Permit Number 17020757
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-15 11:21:501) SHT. A5.1 - WALL FINISHES - 2014 FBC
 SEC.1210.2.2.WALLS AND PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR. THE TABLE NOTES
 "PAINT". CLARIFY.
 2) SHT. A5.1 - DETAIL #7 REFERS TO DETAIL #5 ON A5.1
 FOR RIM HEIGHT OF LAVATORY. DETAIL #5 DOES NOT SHOW A
 LAVATORY. SEE DETAIL #6 ALSO.CLARIFY.
 3) SHT. A5.1 - THE HEIGHT OF THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014
 FBC -ACCESS. SEC.609.4.
 4) SHT. A5.1 - DETAIL #2 & #3 - SHOW THE LENGTH AND
 WIDTH DIMENSIONS OF THE HANDICAP ACCESSIBLE STALLS.
 COMPLY WITH FL. ACCESS. CODE.
 5) THE COVER SHEET C1 LISTS PLUMBING SHEETS P1, P1.1,
 P2, P3, P3.2, & GP1. THESE SHEETS ARE NOT INCLUDED IN
 THE PLAN SET. A THOROUGH PLUMBING PLAN REVIEW CANNOT BE
 DONE WITHOUT THESE SHEETS. SUBMIT ALL REQUIRED SHEETS
 FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  