| 2017-02-22 10:23:21 | PLEASE NOTE THAT THE SERVICE CONDUCTORS SHOWN AT 250MCM | | | IS UNDERSIZED FOR THE 281AMP LOAD BASED ON OPTIONAL | | | MULTIFAMILY DWELLING CALCULATIONS. A 300 CONDUCTOR MUST | | | BE INSTALLED PER NEC 310.15B16 TABLE OF AMPACITIES. | | | | | | SHOW CALCULATIONS BASED ON NEC 220.84 OPTINAL | | | CALCULATION TO APPLY DEMAND FACTORS(45%) | | | | | | CLARIFY IF THERE ARE SMOKES IN THE DWELLING UNITS, IF | | | SO PROVIDE A NOTE TO CLARIFY. THEY WILL BE REQUIRED IF | | | NOT. FBC RES 314-315 | | | | | | SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE. | | | NEC 250.94 | | | | | | | | | | | | VAL PEREZ | | | *6717 |
|