| Plan Review Notes For Permit 17020752 |
| Permit Number |
17020752 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-18 03:35:27 | 1) SUBMIT SIZING CALCULATIONS FOR THE INTERCEPTOR. | | | COMPLY WITH F.A.C. 64E-6 OR PDI STANDARD G101. | | | 2) GREASE INTERCEPTOR CAPACITY SHALL COMPLY WITH 2014 | | | FBC-PLUMBING SEC.1003.3.4.1 & TABLE 1003.3.4.1. | | | 3) INDICATE ON THE SUBMITTED SPECIFICATION SHEET WHICH | | | MODEL OF THE GREASE TRAP IS BEING INSTALLED. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 4) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE | | | INTERCEPTOR.WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) SUBMIT A SANITARY RISER DIAGRAM SHOWING HOW THIS | | | WILL BE CONNECTED TO THE SANITARY SYSTEM. | | | 6) IS THIS REPLACING AN EXISTING UNIT OR IS THIS A NEW | | | INSTALLLATION. INDICATE SUCH ON THE REQUIRED FLOOR | | | PLAN. | | | 7) WHAT TYPE OF FIXTURE(S) IS DISCHARGING INTO THIS | | | INTERCEPTOR? SHOW ON THE REQUIRED FLOOR PLAN. | | | 8) SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS,DISHES, POTS, PANS OR SERVICE WARE USED IN THE | | | PREPARATION, SERVING OR EATING OF FOOD SHALL DDISCHARGE | | | INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK TO THE | | | DRAINAGE SYSTEM. 2014 FBC-PLUMBING SEC.802.1.8. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|