| Plan Review Notes For Permit 17020721 |
| Permit Number |
17020721 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-18 03:08:42 | 1) SUBMIT A FLOOR PLAN SHOWING THE AREAS WHERE THE WORK | | | WILL BE DONE. THE FLOOR PLAN CAN BE HAND DRAWN. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 2) WHY ARE YOU SUBMITTING A SANITARY RISER OF THE | | | UNDERGROUND SANITARY SYSTEM? THIS DOES NOT SHOW ME THE | | | SCOPE OF WORK TO BE DONE. | | | 3) WILL THERE BE ANY WALL REPAIR/TILE REPLACEMENT FOR | | | THE TUB REMOVAL & REPLACEMENT? IF SO, INDICATE SUCH ON | | | THE FLOOR PLAN. A SEPARATE PERRMIT MAY REQUIRED FOR | | | THIS WORK. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) THE NEW SHOWER VALVE SHALL BE OF THE PRESSURE | | | BALANCE, THERMOSTATIC-MIXING OR COMBINATION | | | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPE. 2014 | | | FBC-R SEC. P2708.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|