2017-03-08 16:20:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020715
 3/8/17
  
 1) REFER TO SECTION 501.3.1 AND INDICATE THE
 TERMINATION LOCATION OF THE NEW GARAGE EXHAUST OUTLETS.
  
 2) THE AIR KING BFQ110FAN SPECIFIED ON THE PLAN IS A
 BATHROOM FAN THAT IS LIMITED TO EXHAUSTING A MAXIMUM OF
 125 SQ. FT PER MANUFACTURER'S SPECIFICATIONS. PLEASE
 PROVIDE A FAN RATED FOR USE IN A GARAGE WITH ADEQUATE
 CAPACITY.
  