| 2017-04-19 14:00:41 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17020696 |
| | 4/19/17 |
| | |
| | 1) THE REVISED PLANS ARE STILL INDICATING THE EXISTING |
| | 14" BOILER FLUE VENT IS STILL UNDERSIZED. PLEASE REFER |
| | TO TABLE 504.2 (1) FBC-14 FUEL GAS WHICH INDICATES A |
| | 14" FLUE AT 15' HEIGHT AND 5' LATERAL CAN ADEQUATELY |
| | VENT UP TO 1,327 MBH BASED ON APPLIANCE INPUT RATING. |
| | THIS NUMBER WILL DECREASE USING A 12' FLUE LENGTH AND |
| | ALSO USING A 12" CONNECTOR AS INDICATED ON THE PLANS- |
| | SEE SECTION 504.2.8 : |
| | |
| | 504.2.8 VENT AREA AND DIAMETER. |
| | WHERE THE VERTICAL VENT HAS A LARGER DIAMETER THAN THE |
| | VENT CONNECTOR, THE VERTICAL VENT DIAMETER SHALL BE |
| | USED TO DETERMINE THE MINIMUM VENT CAPACITY, AND THE |
| | CONNECTOR DIAMETER SHALL BE USED TO DETERMINE THE |
| | MAXIMUM VENT CAPACITY. THE FLOW AREA OF THE VERTICAL |
| | VENT SHALL NOT EXCEED SEVEN TIMES THE FLOW AREA OF THE |
| | LISTED APPLIANCE CATEGORIZED VENT AREA, FLUE COLLAR |
| | AREA OR DRAFT HOOD OUTLET AREA UNLESS DESIGNED IN |
| | ACCORDANCE WITH APPROVED ENGINEERING METHODS. |
| | |
| | 2) COMMENTS #5 & 6 FROM THE PREVIOUS REVIEW STILL |
| | EXIST. PLEASE REVISE SHEET M-5 TO SHOW THE DETAILS AND |
| | DIMENSIONS THAT ARE INDICATED IN THE NARRATIVE REPONSE. |
| | PLEASE NOTE THAT THE 8-1/2 X 11" SUBMITTAL DOES NOT |
| | PROVIDE: A) ATTACHMENT DETAILS FOR THE COOLING TOWER TO |
| | THE STRUCTURE. B) THE CLEARANCE DISTANCE HEIGHT FROM |
| | THE ROOF SURFACE. C) DOES NOT BEAR THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL WHO DREW THE PLAN. |
| | |