| 2017-03-14 06:51:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. PROVIDE INFORMATION REGARDING THE TIMELINE FOR THIS |
| | PROJECT. WHEN WILL THE BUILDOUT PERMIT BE SUBMITTED? |
| | SEE COMMENT REGARDING ELEVATOR LOBBIES. AS THE ELEVATOR |
| | LOBBY IS PART OF THE LIFE SAFETY SYSTEM, AND IT APPEARS |
| | THAT APPLICANT PROPOSES TO DEMOLISH THE LOBBIES, |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2. REVISE PLAN TO NOTE WHETHER THIS BUILDING IS A HIGH |
| | RISE OR A MID RISE, FBC 107. |
| | |
| | 3. REVISE PLAN TO INCLUDE METHOD OF COMPLIANCE FOR THE |
| | RENOVATION, FBC EB CHAPTER 5. IT APPEARS THAT THIS WILL |
| | BE A LEVEL III ALTERATION AND A CHANGE OF OCCUPANCY. |
| | |
| | 4. PLAN PROPOSES TO REMOVE THE ELEVATOR LOBBIES. SEE |
| | FBC B 713.14.1. ARE THE ELEVATOR LOBBIES REQUIRED, OR |
| | IS IT EXEMPTED? IF EXEMPT, REVISE PLAN TO INCLUDE |
| | EXEMPTION. IF NOT EXEMPT, REVISE PLAN TO INCLUDE INTENT |
| | THAT THE ELEVATOR LOBBIES WILL BE RESTORED IN |
| | RENOVATION, OR MADE EXEMPT VIA RENOVATION (AND INCLUDE |
| | EXEMPTION), OR REVISE PLAN TO STATE THAT NO FLOOR WILL |
| | BE OCCUPIED UNTIL ALL ELEVATOR LOBBIES ARE RESTORED. |
| | |
| | 5. FS481, INCLUDE THE ARCHITECT BUSINESS NUMBER IN THE |
| | TITLE BLOCK. |
| | |
| | |
| | |
| | |