Plan Review Notes
Plan Review Notes For Permit 17020652
Permit Number 17020652
Review Stop E
Sequence Number 3
Notes
Date Text
2017-10-27 08:39:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL RISER DIAGRAM SHOWS A 1/0 WIRE FOR THE
 200 AMP PANEL. 1/0 WIRE IS NOT RATED FOR A 200 AMP
 SERVICE. PROVIDE CORRECTION. NEC 310.15(B)(7) AND
 (B)(15); FBC RE TABLE E3601.3
 2. ELECTRICAL RISER DIAGRAM SHOWS A # 6 GROUNDING
 ELECTRODE CONDUCTOR (GEC). BASED ON COMMENT # 1 AND THE
 INCREASED WIRE SIZE THAT WILL BE REQUIRED FOR THE
 SERVICE, THIS WIRE IS TOO SMALL. PROVIDE CORRECTION.
 NEC 250.66; FBC RE TABLE E3601.3
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 4. ELECTRICAL RISER DIAGRAM DOES NOT MATCH WHAT IS
 DRAWN ON PLAN. PLAN SHOWS A METER CAN, DISCONNECT, AND
 INTERIOR PANEL. RISER SHOWS A METER CAN AND MAIN
 BREAKER PANEL. CLARIFY AND/OR CORRECT. FBC 107.2.1; NEC
 215.5
 5. LOAD CALCULATION PROVIDED IS NOT CORRECT. LOAD
 CALCULATION IS MISSING SEVERAL ITEMS AND NOT PREPARED
 PROPERLY. SEE FBC RESIDENTIAL OR THE NEC FOR EXAMPLE.
 PROVIDE CORRECTED LOAD CALCULATION WITH ALL LOADS
 INCLUDED. NEC 220; FBC RE3602.3
 6. PANEL SCHEDULE CALLS FOR A 30 AMP BREAKER FOR WATER
 HEATER. BASED ON THE LOAD OF THIS UNIT STATED, THIS
 BREAKER IS TOO SMALL. PROVIDE ACCURATE OCP FOR THE
 TANKLESS WATER HEATER. NEC 110.3, 210.20, 240.4; FBC RE
 3705.5
 7. PANEL SCHEDULE SHOWS A WINDOW UNIT AC. PLAN SHOWS AN
 A/C UNIT WITH AHU. CLARIFY AND/OR CORRECT. PROVIDE ALL
 CIRCUITS AND LOADS IN PANEL SCHEDULE. FBC 107.2.1; NEC
 220; FBC RE 3602.3
 8. PANEL SCHEDULE SHOWS ONLY ONE LIGHTING CIRCUIT.
 BASED ON SQUARE FOOTAGE OF HOME, A MINIMUM OF 2
 LIGHTING CIRCUITS WOULD BE REQUIRED. ADDITIONALLY, THE
 2 SMALL APPLIANCE CIRCUITS REQUIRED ARE NOT SHOWN. SHOW
 ALL REQUIRED BRANCH CIRCUITS IN PANEL SCHEDULE AND LOAD
 CALCULATION. FBC 107.2.1; NEC 220; FBC RE 3602.3
 9. SHEET E-1 STATES THAT THIS IS A DEMO PLAN, BUT NEW
 WORK INSTALLED IS SHOWN. REMOVE CONFLICTING STATEMENT.
 FBC 107.2.1
 10. ELECTRICAL NOTE 3 STATES THAT RECEPTACLES SHALL BE
 TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION DOES
 NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  