2017-07-18 17:58:22FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM SHOWS BARN PANEL?
  
 100A PANEL SCHEDULE IS WHICH BUILDING?
  
 100A PANEL SCHEDULE HAS SEVERAL LOADS EITHER UNDERSIZED
 ON BREAKER OR TOO LARGE OF A BREAKER.
  
 LOAD CALCULATION REQUIRED FOR 200A SERVICE.
  
 OUTLET SPACING ON FLOOR PLAN SHOWN DOES NOT MEET CODE.
  
 IF BARN WORK IS GOING ON WE NEED A FLOOR PLAN FOR
 BARN..
2017-07-13 14:41:51NEW DRAWINGS SUBMITTED. JG.