| Plan Review Notes For Permit 17020652 |
| Permit Number |
17020652 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-18 17:58:22 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM SHOWS BARN PANEL? | | | | | | 100A PANEL SCHEDULE IS WHICH BUILDING? | | | | | | 100A PANEL SCHEDULE HAS SEVERAL LOADS EITHER UNDERSIZED | | | ON BREAKER OR TOO LARGE OF A BREAKER. | | | | | | LOAD CALCULATION REQUIRED FOR 200A SERVICE. | | | | | | OUTLET SPACING ON FLOOR PLAN SHOWN DOES NOT MEET CODE. | | | | | | IF BARN WORK IS GOING ON WE NEED A FLOOR PLAN FOR | | | BARN.. | | 2017-07-13 14:41:51 | NEW DRAWINGS SUBMITTED. JG. |
|