| Plan Review Notes For Permit 17020633 |
| Permit Number |
17020633 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-06 14:33:33 | THE FOLLOWING ITEMS NEED TO BE CORRECTED: | | | | | | FBC EC 2014 | | | C 405.2.2.2 OCCUPANCY SENSORS REQUIRED | | | C 405.5.2 INTERIOR POWER ALLOWANCES PER TABLE 405.5.2 | | | (1) | | | | | | NEC 2011 | | | 110.24(A)(B) AVAILABLE FAULT CURRENT FOR SERVICE | | | REQUIRED | | | 215.5 DIAGRAM OF SERVICE TO BAY/UNIT. | | | 408.4 PANEL SCHEDULE. | | | | | | JAKE LEAHY | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLANS EXAMINER |
|