Plan Review Notes
Plan Review Notes For Permit 17020633
Permit Number 17020633
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-06 14:33:33THE FOLLOWING ITEMS NEED TO BE CORRECTED:
  
 FBC EC 2014
 C 405.2.2.2 OCCUPANCY SENSORS REQUIRED
 C 405.5.2 INTERIOR POWER ALLOWANCES PER TABLE 405.5.2
 (1)
  
 NEC 2011
 110.24(A)(B) AVAILABLE FAULT CURRENT FOR SERVICE
 REQUIRED
 215.5 DIAGRAM OF SERVICE TO BAY/UNIT.
 408.4 PANEL SCHEDULE.
  
 JAKE LEAHY
 CITY OF WEST PALM BEACH
 ELECTRICAL PLANS EXAMINER