| 2017-05-24 12:15:28 | 218 CLEMATIS STREET |
| | PERMIT #17020623 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PRODUCT DATA FOR THE FIRE PIT INDICATES IT IS ONLY |
| | TO BE INSTALLED OUTDOORS. ADDITIONALLY THIS OFFICE DOES |
| | NOT SUPPORT THE USE OF INTERIOR OPEN FLLAME DEVICES. |
| | |
| | SHEET E301: NO EMERGENCY LIGHTING PROVIDED. |
| | |
| | NFPA 96 SECTION 14.1.5 WHERE A SOLID FUEL COOKING |
| | APPLIANCE ALLOWS EFFLUENT TO ESCAPE FROM THE APPLIANCE |
| | OPENING, THIS OPENING SHALL BE COVERED BY A HOOD AND AN |
| | EXHAUST SYSTEM THAT MEETS THE REQUIREMENTS OF SECTIONS |
| | 14.3, 14.4, AND 14.6.14.7.1 SOLID FUEL COOKING |
| | APPLIANCES THAT PRODUCE GREASELADEN VAPORS SHALL BE |
| | PROTECTED BY LISTED FIRE-EXTINGUISHING EQUIPMENT. NO |
| | TYPE I EXHAUST HOOD WITH SUPPRESSION SYSTEM PROVIDED |
| | FOR WOOD FIRED PIZZA OVENS. |
| | |
| | SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH |
| | NFPA 96. APPLIANCES WITH FIREBOXES OVER 5 FT3 THE WATER |
| | SOURCE SHALL BE A FIXED PIPE WATER SYSTEM WITH A HOSE |
| | OF ADEQUATE LENGTH TO REACH THE COMBUSTION AND COOKING |
| | CHAMBERS OF THE APPLIANCE. ALL OVEN ASH SHALL BE |
| | REMOVED FROM THE ASH COMPARTMENT AT LEAST ONCE PER DAY. |
| | THE ASH SHALL BE SPRAYED ADEQUATELY WITH WATER BEFORE |
| | REMOVAL TO EXTINGUISH ANY HOT ASH OR CINDERS AND TO |
| | CONTROL THE DUST WHEN THE ASH IS MOVED. SECTION |
| | 14.9.3.8.1 A HEAVY METAL CONTAINER OR CART (MINIMUM 16 |
| | GAUGE) WITH A COVER SHALL BE PROVIDED FOR THE REMOVAL |
| | OF ASH. THE ASH REMOVAL CONTAINER OR CART SHALL NOT |
| | EXCEED A MAXIMUM OF 20 GAL CAPACITY, SHALL BE ASSIGNED |
| | FOR THIS ONE PURPOSE, SHALL BE ABLE TO BE HANDLED |
| | EASILY BY ANY EMPLOYEE ASSIGNED THE TASK, AND SHALL |
| | PASS EASILY THROUGH ANY PASSAGEWAY TO THE OUTSIDE OF |
| | THE BUILDING. THE CONTAINER OR CART SHALL ALWAYS BE |
| | COVERED WHEN IT IS BEING MOVED THROUGH THE PREMISES. |
| | |
| | NO FIRE ALARM OR FIRE SPRINKLER SCOPE OF WORK PROVIDED. |
| | |
| | EXISTING EXIT DOORS: FOR ASSEMBLY OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| | LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| | EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| | AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| | IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |