Plan Review Notes
Plan Review Notes For Permit 17020623
Permit Number 17020623
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-01 16:34:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020623 CHANGE OF OCCUPANCY!!!
 ADD: 218 CLEMATIS ST.
 CONT: MCL CONSTRUCTION INC.
 TEL: 561-368-2434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 01/ 2017
 ACTION: DENIED
  
 1A-B) COMPLIED.
  
 1C) NEW COMMENT WHICH DEALS WITH THE AREA INCREASE
 TAKEN FOR FIRE SPRINKLERS, NO PLANS WERE SUBMITTED FOR
 FIRE SPRINKLERS. W. P. B. ADMINISTRATIVE
 CODE105.3.1.2(2) FIRE SPRINKLER DOCUMENTS FOR ANY NEW
 BUILDING OR ADDITION WHICH INCLUDES A FIRE SPRINKLER
 SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER HEADS. A
 CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED
 UNDER SECTION 633.521, FLORIDA STATUTES, MAY DESIGN A
 FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, NOT
 WITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 2) 2ND REQUEST. PLEASE NOTE THE ENERGY FORMS STATE
 RIGHT BY THE SIGNATURE, THIS SIGNATURE IS AN ELECTRONIC
 SIGNATURE. THE SUBMITTED ENERGY CALS. AND HVAC CALS.
 ARE PRINTED BUT HAVE A DIGITAL SIGNATURE, BY JOHN
 LANGFORD P. E. PLEASE SHOW COMPLIANCE WITH FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEES SIGNATURE SHALL NOT BE USED ON ELECTRONICALLY
 SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET A0.3 SHOWS 127 INTERIOR SEATS, 26 EXTERIOR
 SEATS AND WHAT MAY APPEAR TO BE 30 FEET OF STANDING AT
 THE BAR, UNDETERMINABLE AMOUNT OF FOOTAGE AND USE?
  
 3A-C) COMPLIED
  
 3D) PLEASE NOTE THE FIRE PLAN REVIEWERS NOTES ON THE
 FIRE PIT. THE PLANS SHOW IN THE CENTER OF THE PLAN A
 INDOOR FIRE PIT, PLEASE PROVIDE THE TYPE OF FUEL,
 AMOUNT OF FUEL AND THE AMOUNT OF BTU?S WILL BE USED PER
 HOUR. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 4-6) COMPLIED.
  
 7A) SEMI-COMPLIED. IT IS TRUE THE FRONT ENTRY DOOR DOES
 NOT REQUIRE PANIC HARDWARE BUT THE HARDWARE DOES NEED
 TO COMPLY WITH : 2014 FBC-B SECTION 1008.1.9.3(2)
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
  
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
  
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
  
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 7B) THE REAR EXIT DOOR NOT LABELED ON SHEET A0.5 AND
 NOT INCLUDED IN THE DOOR SCHEDULE SHEET A7.1 DOES
 INDICATE A DOOR 108 TO BE VERIFIED PANIC HARDWARE IS
 REQUIRED. PLEASE IDENTIFY THE DOOR ON SHEET A0.5.
  
 8) COMPLIED.
  
 8A) NEW COMMENT DEALS WITH A0.5 THE AWNING OVER THE
 PUBLIC SIDEWALK AND HOW CLOSE THE CURB IS TO THE
 AWNING. THE CURB IS NOT SHOWN IN THE DEPICTED PLAN.
 COMPLIANCE WITH 2014 FBC-B SECTION 3202.3.1 CANNOT BE
 DETERMINED.
 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND SIGNS.
 AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE
 CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS
 SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES
 AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE
 ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE
 THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM
 THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT
 AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED
 NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE.
  
  
 9) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. 61-41,003
 ADMINISTRATION AND DEPARTMENT RESPONSIBILITIES. (4)
 TESTING & EVALUATION OF PRODUCTS. FL. S. 553.842
 PRODUCT EVALUATION AND APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 ROOF TOP VENTILATORS & FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 11) SEMI-COMPLIED. THE ROOF TOP EXHAUST FAN DOES HAVE A
 DETAIL FOR ANCHORING OF THE FAN TO THE CURB AND CURB TO
 THE ROOF FRAMING. THE MECHANICAL REVIEWER REQUEST
 DETAILS AS WELL FOR THE NEW ROOF TOP CONDENSERS TO THE
 EXISTING STANDS.
 ROOF TOP A/C STANDS WILL NEED TO SUPPLY THE FOLLOWING
 INFORMATION, CALCULATE THE AREA OF THE ROOF TOP
 COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND
 COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN
 THE TABLES , ANCHORS AND UPLIFT VERSES MOMENT. 2014
 FBC-B 1604.4 ANALYSIS.
  
 12) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  