| 2017-06-01 16:34:07 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17020623 CHANGE OF OCCUPANCY!!! |
| | ADD: 218 CLEMATIS ST. |
| | CONT: MCL CONSTRUCTION INC. |
| | TEL: 561-368-2434 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JUNE 01/ 2017 |
| | ACTION: DENIED |
| | |
| | 1A-B) COMPLIED. |
| | |
| | 1C) NEW COMMENT WHICH DEALS WITH THE AREA INCREASE |
| | TAKEN FOR FIRE SPRINKLERS, NO PLANS WERE SUBMITTED FOR |
| | FIRE SPRINKLERS. W. P. B. ADMINISTRATIVE |
| | CODE105.3.1.2(2) FIRE SPRINKLER DOCUMENTS FOR ANY NEW |
| | BUILDING OR ADDITION WHICH INCLUDES A FIRE SPRINKLER |
| | SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER HEADS. A |
| | CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, CERTIFIED |
| | UNDER SECTION 633.521, FLORIDA STATUTES, MAY DESIGN A |
| | FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY |
| | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, |
| | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, NOT |
| | WITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 2) 2ND REQUEST. PLEASE NOTE THE ENERGY FORMS STATE |
| | RIGHT BY THE SIGNATURE, THIS SIGNATURE IS AN ELECTRONIC |
| | SIGNATURE. THE SUBMITTED ENERGY CALS. AND HVAC CALS. |
| | ARE PRINTED BUT HAVE A DIGITAL SIGNATURE, BY JOHN |
| | LANGFORD P. E. PLEASE SHOW COMPLIANCE WITH FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED, |
| | FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE |
| | LICENSEES SIGNATURE SHALL NOT BE USED ON ELECTRONICALLY |
| | SIGNED AND SEALED ENGINEERING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3) SHEET A0.3 SHOWS 127 INTERIOR SEATS, 26 EXTERIOR |
| | SEATS AND WHAT MAY APPEAR TO BE 30 FEET OF STANDING AT |
| | THE BAR, UNDETERMINABLE AMOUNT OF FOOTAGE AND USE? |
| | |
| | 3A-C) COMPLIED |
| | |
| | 3D) PLEASE NOTE THE FIRE PLAN REVIEWERS NOTES ON THE |
| | FIRE PIT. THE PLANS SHOW IN THE CENTER OF THE PLAN A |
| | INDOOR FIRE PIT, PLEASE PROVIDE THE TYPE OF FUEL, |
| | AMOUNT OF FUEL AND THE AMOUNT OF BTU?S WILL BE USED PER |
| | HOUR. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4-6) COMPLIED. |
| | |
| | 7A) SEMI-COMPLIED. IT IS TRUE THE FRONT ENTRY DOOR DOES |
| | NOT REQUIRE PANIC HARDWARE BUT THE HARDWARE DOES NEED |
| | TO COMPLY WITH : 2014 FBC-B SECTION 1008.1.9.3(2) |
| | 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT |
| | LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN |
| | PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR |
| | DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED |
| | LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED: |
| | |
| | 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS |
| | LOCKED; |
| | |
| | 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE |
| | EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS |
| | DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE |
| | SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A |
| | CONTRASTING BACKGROUND; AND |
| | |
| | 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS |
| | REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE. |
| | |
| | 7B) THE REAR EXIT DOOR NOT LABELED ON SHEET A0.5 AND |
| | NOT INCLUDED IN THE DOOR SCHEDULE SHEET A7.1 DOES |
| | INDICATE A DOOR 108 TO BE VERIFIED PANIC HARDWARE IS |
| | REQUIRED. PLEASE IDENTIFY THE DOOR ON SHEET A0.5. |
| | |
| | 8) COMPLIED. |
| | |
| | 8A) NEW COMMENT DEALS WITH A0.5 THE AWNING OVER THE |
| | PUBLIC SIDEWALK AND HOW CLOSE THE CURB IS TO THE |
| | AWNING. THE CURB IS NOT SHOWN IN THE DEPICTED PLAN. |
| | COMPLIANCE WITH 2014 FBC-B SECTION 3202.3.1 CANNOT BE |
| | DETERMINED. |
| | 3202.3.1 AWNINGS, CANOPIES, MARQUEES AND SIGNS. |
| | AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE |
| | CONSTRUCTED SO AS TO SUPPORT APPLICABLE LOADS AS |
| | SPECIFIED IN CHAPTER 16. AWNINGS, CANOPIES, MARQUEES |
| | AND SIGNS WITH LESS THAN 15 FEET (4572 MM) CLEARANCE |
| | ABOVE THE SIDEWALK SHALL NOT EXTEND INTO OR OCCUPY MORE |
| | THAN TWO-THIRDS THE WIDTH OF THE SIDEWALK MEASURED FROM |
| | THE BUILDING. STANCHIONS OR COLUMNS THAT SUPPORT |
| | AWNINGS, CANOPIES, MARQUEES AND SIGNS SHALL BE LOCATED |
| | NOT LESS THAN 2 FEET (610 MM) IN FROM THE CURB LINE. |
| | |
| | |
| | 9) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. 61-41,003 |
| | ADMINISTRATION AND DEPARTMENT RESPONSIBILITIES. (4) |
| | TESTING & EVALUATION OF PRODUCTS. FL. S. 553.842 |
| | PRODUCT EVALUATION AND APPROVAL. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, |
| | ROOF TOP VENTILATORS & FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 11) SEMI-COMPLIED. THE ROOF TOP EXHAUST FAN DOES HAVE A |
| | DETAIL FOR ANCHORING OF THE FAN TO THE CURB AND CURB TO |
| | THE ROOF FRAMING. THE MECHANICAL REVIEWER REQUEST |
| | DETAILS AS WELL FOR THE NEW ROOF TOP CONDENSERS TO THE |
| | EXISTING STANDS. |
| | ROOF TOP A/C STANDS WILL NEED TO SUPPLY THE FOLLOWING |
| | INFORMATION, CALCULATE THE AREA OF THE ROOF TOP |
| | COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND |
| | COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN |
| | THE TABLES , ANCHORS AND UPLIFT VERSES MOMENT. 2014 |
| | FBC-B 1604.4 ANALYSIS. |
| | |
| | 12) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |