| 2017-03-17 09:12:43 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. DOOR ON ACCESSIBLE TOILET STALLS SHALLL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR |
| | ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | REQUIRED TURNING SPACE. PER FBC ACC 603.2.3 |
| | |
| | 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE, PER FBC ACC 609.4 |
| | |
| | 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. PER FBC ACC 604.7 |
| | |
| | 4. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602. |
| | PER FBC ACC 602.1 |
| | |
| | 5. ALL FIXTURE FLOWING THROUGH GREASE INTERCEPTOR SHALL |
| | BE INCLUDED ON THE SIZING CALCULATION THE FIXTURES THAT |
| | ARE MISSING FROM CALCULATIONS ARE # 4 MOP SINK, #6.1 |
| | SINK, #6.2 SINK, #7 PRE RINSE SINK, #8 DISHWASHER , #12 |
| | SINK , #32.A TROUGH DRAIN. PER FBC PL 1003.3.1 |
| | |
| | 6. FIXTURES IN THE BAR AREA SHALL NOT BE ON THE GREASE |
| | SYSTEM. PER FBC PL 1003.2 |
| | |
| | 7. THE THREE COMP SINK SHALL BE INDIRECTLY WASTED. PER |
| | FBC PL 802.1 |
| | |
| | 8. SHT. P101 DETAIL B5 THE FIRST NOTE REQUIRING |
| | TEMPERED WATER IS WRONG THE TEMPERATURE FOR TEMPERED |
| | WATER SHAL BE BETWEEN 85?F (29?C) AND 110?F (43?C). PER |
| | FBC PL 202 |
| | |
| | 9. SHOW TEMPERATURE LIMITING DEVICE ON WATER RISER |
| | DIAGRAM TO SHOW COMPLIANCE WITH FBC PL 416.5 |
| | |
| | 10. SHOW COMPLIANCE WITH FBC PL 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |