 PLUMBING COMMENTS:
  
 1. DOOR ON ACCESSIBLE TOILET STALLS SHALLL NOT SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE. DOORS SHALL BE PERMITTED TO SWING INTO THE
 REQUIRED TURNING SPACE. PER FBC ACC 603.2.3
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE, PER FBC ACC 609.4
  
 3. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW. PER FBC ACC 604.7
  
 4. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602.
 PER FBC ACC 602.1
  
 5. ALL FIXTURE FLOWING THROUGH GREASE INTERCEPTOR SHALL
 BE INCLUDED ON THE SIZING CALCULATION THE FIXTURES THAT
 ARE MISSING FROM CALCULATIONS ARE # 4 MOP SINK, #6.1
 SINK, #6.2 SINK, #7 PRE RINSE SINK, #8 DISHWASHER , #12
 SINK , #32.A TROUGH DRAIN. PER FBC PL 1003.3.1
  
 6. FIXTURES IN THE BAR AREA SHALL NOT BE ON THE GREASE
 SYSTEM. PER FBC PL 1003.2
  
 7. THE THREE COMP SINK SHALL BE INDIRECTLY WASTED. PER
 FBC PL 802.1
  
 8. SHT. P101 DETAIL B5 THE FIRST NOTE REQUIRING
 TEMPERED WATER IS WRONG THE TEMPERATURE FOR TEMPERED
 WATER SHAL BE BETWEEN 85?F (29?C) AND 110?F (43?C). PER
 FBC PL 202
  
 9. SHOW TEMPERATURE LIMITING DEVICE ON WATER RISER
 DIAGRAM TO SHOW COMPLIANCE WITH FBC PL 416.5
  
 10. SHOW COMPLIANCE WITH FBC PL 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  