2017-03-17 09:22:30GAS COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC FUEL GAS 404.8.2 CONDUIT
 WITH BOTH ENDS TERMINATING INDOORS.
 WHERE THE CONDUIT ORIGINATES AND TERMINATES WITHIN THE
 SAME BUILDING, THE CONDUIT SHALL ORIGINATE AND
 TERMINATE IN AN ACCESSIBLE PORTION OF THE BUILDING AND
 SHALL NOT BE SEALED. THE CONDUIT SHALL EXTEND NOT LESS
 THAN 2 INCHES (51 MM) BEYOND THE POINT WHERE THE PIPE
 EMERGES FROM THE FLOOR.
  
 2, SHOW ROUTING FROM METER TO STEP DOWN REGULATOR NOT
 SHOWN ON SITE PLAN. PER WPB AMEND TO FBC 107,2,1
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 1ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  