2017-03-01 11:25:59218 CLEMATIS STREET
 PERMIT #17020623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT EXIT DOORS.
  
 INSUFFICIENT EXIT SIGNS PROVIDED TO IDENTIFY PRIMARY
 AND SECONDARY EXITS. NO EMERGENCY LIGHTING PROVIDED.
  
 PROVIDE MORE INFORMATION AND DETAILS FOR THE FIREPIT.
 SUBMIT PRODUCT DATA AND UL LISTING (OR EQUAL).
  
 PROVIDE UL LISTING (OR EQUAL) DATA FOR THE PIZZA OVENS.
 SUBMIT PRODUCT DATA FOR WOOD FIRED PIZZA OVENS
 INDICATING IF A SUPPRESSION SYSTEM IS REQUIRED FOR THIS
 APPLIANCE.
  
 INDICATE THE LOCATION AND QUANTITY OF WOOD FUEL TO BE
 STORED FOR THE PIZZA OVENS.
  
 SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH
 NFPA 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL
 STORAGE SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE
 IS LOCATED IN THE SAME ROOM AS THE SOLID FUELED
 APPLIANCE, OR IN THE SAME ROOMS AS THE FUEL-LOADING OR
 CLEAN-OUT DOORS. SECTION14.9.3.7.3 APPLIANCES WITH
 FIREBOXES OVER 5 FT3 THE WATER SOURCE SHALL BE A FIXED
 PIPE WATER SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO
 REACH THE COMBUSTION AND COOKING CHAMBERS OF THE
 APPLIANCE. ALL OVEN ASH SHALL BE REMOVED FROM THE ASH
 COMPARTMENT AT LEAST ONCE PER DAY. THE ASH SHALL BE
 SPRAYED ADEQUATELY WITH WATER BEFORE REMOVAL TO
 EXTINGUISH ANY HOT ASH OR CINDERS AND TO CONTROL THE
 DUST WHEN THE ASH IS MOVED. SECTION 14.9.3.8.1 A HEAVY
 METAL CONTAINER OR CART (MINIMUM 16 GAUGE) WITH A COVER
 SHALL BE PROVIDED FOR THE REMOVAL OF ASH. THE ASH
 REMOVAL CONTAINER OR CART SHALL NOT EXCEED A MAXIMUM OF
 20 GAL CAPACITY, SHALL BE ASSIGNED FOR THIS ONE
 PURPOSE, SHALL BE ABLE TO BE HANDLED EASILY BY ANY
 EMPLOYEE ASSIGNED THE TASK, AND SHALL PASS EASILY
 THROUGH ANY PASSAGEWAY TO THE OUTSIDE OF THE BUILDING.
 THE CONTAINER OR CART SHALL ALWAYS BE COVERED WHEN IT
 IS BEING MOVED THROUGH THE PREMISES.
  
 MEP PLANS ARE SIGNED; HOWEVER, THE SEAL IS A COPY OF
 THE SEAL.
  
 NO FIRE ALARM OR FIRE SPRINKLER SCOPE OF WORK PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW