| 2017-03-01 11:25:59 | 218 CLEMATIS STREET |
| | PERMIT #17020623 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF |
| | THE FIRE MARSHAL. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT EXIT DOORS. |
| | |
| | INSUFFICIENT EXIT SIGNS PROVIDED TO IDENTIFY PRIMARY |
| | AND SECONDARY EXITS. NO EMERGENCY LIGHTING PROVIDED. |
| | |
| | PROVIDE MORE INFORMATION AND DETAILS FOR THE FIREPIT. |
| | SUBMIT PRODUCT DATA AND UL LISTING (OR EQUAL). |
| | |
| | PROVIDE UL LISTING (OR EQUAL) DATA FOR THE PIZZA OVENS. |
| | SUBMIT PRODUCT DATA FOR WOOD FIRED PIZZA OVENS |
| | INDICATING IF A SUPPRESSION SYSTEM IS REQUIRED FOR THIS |
| | APPLIANCE. |
| | |
| | INDICATE THE LOCATION AND QUANTITY OF WOOD FUEL TO BE |
| | STORED FOR THE PIZZA OVENS. |
| | |
| | SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH |
| | NFPA 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL |
| | STORAGE SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE |
| | IS LOCATED IN THE SAME ROOM AS THE SOLID FUELED |
| | APPLIANCE, OR IN THE SAME ROOMS AS THE FUEL-LOADING OR |
| | CLEAN-OUT DOORS. SECTION14.9.3.7.3 APPLIANCES WITH |
| | FIREBOXES OVER 5 FT3 THE WATER SOURCE SHALL BE A FIXED |
| | PIPE WATER SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO |
| | REACH THE COMBUSTION AND COOKING CHAMBERS OF THE |
| | APPLIANCE. ALL OVEN ASH SHALL BE REMOVED FROM THE ASH |
| | COMPARTMENT AT LEAST ONCE PER DAY. THE ASH SHALL BE |
| | SPRAYED ADEQUATELY WITH WATER BEFORE REMOVAL TO |
| | EXTINGUISH ANY HOT ASH OR CINDERS AND TO CONTROL THE |
| | DUST WHEN THE ASH IS MOVED. SECTION 14.9.3.8.1 A HEAVY |
| | METAL CONTAINER OR CART (MINIMUM 16 GAUGE) WITH A COVER |
| | SHALL BE PROVIDED FOR THE REMOVAL OF ASH. THE ASH |
| | REMOVAL CONTAINER OR CART SHALL NOT EXCEED A MAXIMUM OF |
| | 20 GAL CAPACITY, SHALL BE ASSIGNED FOR THIS ONE |
| | PURPOSE, SHALL BE ABLE TO BE HANDLED EASILY BY ANY |
| | EMPLOYEE ASSIGNED THE TASK, AND SHALL PASS EASILY |
| | THROUGH ANY PASSAGEWAY TO THE OUTSIDE OF THE BUILDING. |
| | THE CONTAINER OR CART SHALL ALWAYS BE COVERED WHEN IT |
| | IS BEING MOVED THROUGH THE PREMISES. |
| | |
| | MEP PLANS ARE SIGNED; HOWEVER, THE SEAL IS A COPY OF |
| | THE SEAL. |
| | |
| | NO FIRE ALARM OR FIRE SPRINKLER SCOPE OF WORK PROVIDED. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |