2017-03-10 10:50:30PAGE E101
 A) LOAD CACLUATION PER ARTICLE 220 REQUIRED.
 B) FAULT CURRENT CALCULATION REQUIRED PER 110.24
 C) LABELING FOR FAULT CURRENT REQUIRED PER 100.24
 D) NEED THE GROUNDING DETAIL SHOWN ON DRAWING FOR THE
 SERVICE.
 E) RISER DIAGRAM FEEDER 200 TOO SMALL FOR 400A
 F) RISER DIAGRAM FEEDER 300 NOT SHOWN ON DRAWINGS
 G) TIME CLOCK SUBMIT CUT SHEET
  
 PAGE E201
 A) CIRCUITS AT THE BAR B19,21,23, A48,18,22 REQUIRE
 GFCI PROTECTION 210.8(B)(5)
 B) KITCHEN OUTLETS A29,34,53,58,59, B31,33,35,37
 REQUIRE GFCI PROTECTION 210.8(B)(2)
  
 PAGE E202
 A) ROOF NEEDS AN OUTLET WITHIN 25' OF THE EQUIPMENT AND
 GFCI PROTECTED 210.63, 210.8(B)(3)
  
 PAGE E301
 A) SUBMIT INTERIOR LIGHTING POWER ALLOWANCES PER FBC EC
 C405.5.2
 B) LIGHTING IN BAR AREA NOT CLEAR ON DRAWINGSS LINES
 ALL OVER THE AREA NOT CONNECTED TO ANYTHING.
 C) LIGHT FIXTURE TYPES TO BE LABLELED ON ALL FIXTURES
 ON DRAWING FOR REVIEW.
 D) ALL CIRCUITS ARE SHOWN AS TIME CLOCK NEED CIRCUIT
 NUMBERS ON PLANS FOR LIGHTING.