| 2017-03-10 10:50:30 | PAGE E101 | | | A) LOAD CACLUATION PER ARTICLE 220 REQUIRED. | | | B) FAULT CURRENT CALCULATION REQUIRED PER 110.24 | | | C) LABELING FOR FAULT CURRENT REQUIRED PER 100.24 | | | D) NEED THE GROUNDING DETAIL SHOWN ON DRAWING FOR THE | | | SERVICE. | | | E) RISER DIAGRAM FEEDER 200 TOO SMALL FOR 400A | | | F) RISER DIAGRAM FEEDER 300 NOT SHOWN ON DRAWINGS | | | G) TIME CLOCK SUBMIT CUT SHEET | | | | | | PAGE E201 | | | A) CIRCUITS AT THE BAR B19,21,23, A48,18,22 REQUIRE | | | GFCI PROTECTION 210.8(B)(5) | | | B) KITCHEN OUTLETS A29,34,53,58,59, B31,33,35,37 | | | REQUIRE GFCI PROTECTION 210.8(B)(2) | | | | | | PAGE E202 | | | A) ROOF NEEDS AN OUTLET WITHIN 25' OF THE EQUIPMENT AND | | | GFCI PROTECTED 210.63, 210.8(B)(3) | | | | | | PAGE E301 | | | A) SUBMIT INTERIOR LIGHTING POWER ALLOWANCES PER FBC EC | | | C405.5.2 | | | B) LIGHTING IN BAR AREA NOT CLEAR ON DRAWINGSS LINES | | | ALL OVER THE AREA NOT CONNECTED TO ANYTHING. | | | C) LIGHT FIXTURE TYPES TO BE LABLELED ON ALL FIXTURES | | | ON DRAWING FOR REVIEW. | | | D) ALL CIRCUITS ARE SHOWN AS TIME CLOCK NEED CIRCUIT | | | NUMBERS ON PLANS FOR LIGHTING. |
|