2017-02-21 13:23:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020621 INTERIOR DEMO & STRUCTURE
 ONLY!!!
 ADD: 218 CLEMATIS ST.
 CONT: MCL CONSTRUCTION INC.
 TEL: 561-368-2434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 21/ 2017
 ACTION: DENIED
  
 NOTICE! STRUCTURAL PERMIT ONLY: 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.13 PHASED
 PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS
 AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF
 STRUCTURAL OR ANY OTHER PART OF A BUILDING OR STRUCTURE
 BEFORE THE CONSTRUCTION DOCUMENTS FOR THE WHOLE
 BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER
 OF SUCH PERMIT FOR THE STRUCTURAL PERMIT OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED.
  
 1) THE COVERSHEET LIST THE FLOOR RATING AS A1.0 HOUR
 FIRE RATING PER TABLE 601 OF THE 2014 FBC-B. THE
 COVERSHEET DOES NOT LIST ANY CRITERIA FOR HORIZONTAL
 ASSEMBLIES OR OCCUPANCY SEPARATION FOR HORIZONTAL
 ASSEMBLIES SEPARATING THE A2 ASSEMBLY USE AND THE
 BUSINESS OCCUPANCY ON THE 2ND FLOOR. PLEASE REVIEW
 TABLE 707.310 OF THE FBC-B THE REQUIREMENT FOR 2 HOUR
 FIRE SEPARATION BETWEEN THE HORIZONTAL ASSEMBLIES
 BETWEEN FIRE AREAS. THIS IS A MIXED USE BUILDING PLEASE
 PROVIDE THE TOTAL SQ. FT. FOR EACH OCCUPANCY PER FLOOR
 AND 508.4.2 ALLOWABLE BUILDING AREA. IN EACH STORY, THE
 BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS
 OF THE ACTUAL BUILDING AREA OF EACH SEPARATED OCCUPANCY
 DIVIDED BY THE ALLOWABLE BUILDING AREA OF EACH
 SEPARATED OCCUPANCY SHALL NOT EXCEED 1.
  
 2) IN THE EXISITNG BUILDING CODE SECTION 1012.5.1 FIRE
 WALL ALTERNATIVE FOR HORIZONTAL ASSEMBLIES THERE ARE
 (3) REQUIREMENTS IF ALL (3) REQUIREMENTS ARE MET THAN
 THE HORIZONTAL ASSEMBLIESCAN BE REDUCED TO (1) HOUR.
 PLEASE NOTE THIS TENANT SPACE IS ONLY (1) TENANT SPACE
 OF THE BUILDING ADDRESSED 230 CLEMATIS WITH 18,317
 SQUARE FEET ON THE 1ST FLOOR AND 14,344 ON THE SECOND
 FLOOR.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  