| 2017-02-21 13:23:37 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17020621 INTERIOR DEMO & STRUCTURE |
| | ONLY!!! |
| | ADD: 218 CLEMATIS ST. |
| | CONT: MCL CONSTRUCTION INC. |
| | TEL: 561-368-2434 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 21/ 2017 |
| | ACTION: DENIED |
| | |
| | NOTICE! STRUCTURAL PERMIT ONLY: 2014 FLORIDA BUILDING |
| | CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.13 PHASED |
| | PERMIT APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE |
| | CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS |
| | AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF |
| | STRUCTURAL OR ANY OTHER PART OF A BUILDING OR STRUCTURE |
| | BEFORE THE CONSTRUCTION DOCUMENTS FOR THE WHOLE |
| | BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE HOLDER |
| | OF SUCH PERMIT FOR THE STRUCTURAL PERMIT OR OTHER PARTS |
| | OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE |
| | HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND |
| | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. |
| | |
| | 1) THE COVERSHEET LIST THE FLOOR RATING AS A1.0 HOUR |
| | FIRE RATING PER TABLE 601 OF THE 2014 FBC-B. THE |
| | COVERSHEET DOES NOT LIST ANY CRITERIA FOR HORIZONTAL |
| | ASSEMBLIES OR OCCUPANCY SEPARATION FOR HORIZONTAL |
| | ASSEMBLIES SEPARATING THE A2 ASSEMBLY USE AND THE |
| | BUSINESS OCCUPANCY ON THE 2ND FLOOR. PLEASE REVIEW |
| | TABLE 707.310 OF THE FBC-B THE REQUIREMENT FOR 2 HOUR |
| | FIRE SEPARATION BETWEEN THE HORIZONTAL ASSEMBLIES |
| | BETWEEN FIRE AREAS. THIS IS A MIXED USE BUILDING PLEASE |
| | PROVIDE THE TOTAL SQ. FT. FOR EACH OCCUPANCY PER FLOOR |
| | AND 508.4.2 ALLOWABLE BUILDING AREA. IN EACH STORY, THE |
| | BUILDING AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS |
| | OF THE ACTUAL BUILDING AREA OF EACH SEPARATED OCCUPANCY |
| | DIVIDED BY THE ALLOWABLE BUILDING AREA OF EACH |
| | SEPARATED OCCUPANCY SHALL NOT EXCEED 1. |
| | |
| | 2) IN THE EXISITNG BUILDING CODE SECTION 1012.5.1 FIRE |
| | WALL ALTERNATIVE FOR HORIZONTAL ASSEMBLIES THERE ARE |
| | (3) REQUIREMENTS IF ALL (3) REQUIREMENTS ARE MET THAN |
| | THE HORIZONTAL ASSEMBLIESCAN BE REDUCED TO (1) HOUR. |
| | PLEASE NOTE THIS TENANT SPACE IS ONLY (1) TENANT SPACE |
| | OF THE BUILDING ADDRESSED 230 CLEMATIS WITH 18,317 |
| | SQUARE FEET ON THE 1ST FLOOR AND 14,344 ON THE SECOND |
| | FLOOR. |
| | |
| | 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS. |
| | 2014 FBC-B 2204.1 WELDING |
| | 201404.4.2 BOLTING. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |