| Plan Review Notes For Permit 17020618 |
| Permit Number |
17020618 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-07 18:23:14 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GAF MODIFIED ROOF SYSTEM SPECIFIED HAS A MAXIMUM | | | DESIGN PRESSURE THAT IS NOT ADEQUATE FOR THE PERIMETER | | | AND CORNER ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND | | | SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION | | | NUMBER 7 OF NOA NO. 14-1030.02. FBC 103.2.1 | | | THE CALCULATIONS THAT WERE SUBMITTED ARE INCORRECT. | | | THIS PROJECT IS A TWO STORY ADDITION, THE MEAN ROOF | | | HEIGHT IS AROUND 20 FEET. THE HEIGHT ON THE | | | CALCULATIONS IS SPECIFIED AS 8 FEET. THE PARAPET WALL | | | IS 1' 9" HIGH, NOT 4', THEREFORE, THE UPLIFT PRESSURES | | | IN THE CORNERS ARE NOT THE SAME AS THE PERIMETER | | | PRESSURES. THE BASE SHEET FASTENING FOR THE CORNERS IS | | | SPECIFIED AS 24 STAGGERED ROWS. PLEASE SUBMIT CORRECTED | | | CALCULATIONS AND REVIEW THEM CAREFULLY FOR ERRORS. | | | | | | 2) THE REVISION FEES OF $305.50 WILL NEED TO BE PAID | | | BEFORE ANY MORE PLAN REVIEWS ARE DONE. |
|