2017-02-21 17:33:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - THE PRODUCT APPROVALS ARE REQUIRED TO
 BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 2) THE GAF MODIFIED ROOF SYSTEM SPECIFIED HAS A MAXIMUM
 DESIGN PRESSURE THAT IS NOT ADEQUATE FOR THE PERIMETER
 AND CORNER ROOF AREAS. SUBMIT TWO SETS OF SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY LIMITATION
 NUMBER 7 OF NOA NO. 14-1030.02. FBC 103.2.1
  
 3) FOUR OF THE PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE CHANGES OR WERE NOT PREVIOUSLY SUBMITTED AND ARE
 CONSIDERED REVISIONS. THE BORAL TILESEAL UNDERLAYMENT
 NOA NO. 12-0417.06 AND THE PGT FD-101 FRENCH DOORS NOA
 NO. 16-0629.17 ARE NEW. THE EAGLE ROOFING CAPISTRANO
 CONCRETE TILE NOA NO. 15-0223.20 AND THE PGT
 PW-701/720/820 FIXED WINDOWS NOA NO. 16-0629.14 ARE
 CHANGES. THE REVISION FEE IS $100.00 PLUS $50.00 PER
 PRODUCT APPROVAL. THE TOTAL IS $305.50.
  
  
  