| Plan Review Notes For Permit 17020540 |
| Permit Number |
17020540 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-02-18 03:55:15 | 1) SUBMIT A PIPING DIAGRAM FOR THE PIPING TO BE | | | INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. | | | 2) WILL THERE BE A CONNECTION TO POTABLE WATER? IF SO, | | | A BACKFLOW PREVENTER MAY REQUIRED TO ISOLATE THE | | | HAZARD. 2014 FBC-PLUMBING SECS.608.1, 608.13. 2ND | | | REQUEST. | | | 3) THE SYSTEM SHALL COMPLY WITH 2014 FBC-MECHANICAL | | | SEC.1402.5.1 (PRESSURE & TEMPERATURE RELIEF VALVE). 2ND | | | REQUEST. | | | 4) A VACUUM RELIEF MAY BE REQUIRED ON THE SYSTEM. 2014 | | | FBC-MECH. SEC.1402.5.2. CLARIFY.2ND REQUEST. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|