Plan Review Notes
Plan Review Notes For Permit 17020540
Permit Number 17020540
Review Stop P
Sequence Number 1
Notes
Date Text
2017-02-16 07:31:221) IDENTIFY ON THE COLLECTOR SPECIFICATION SHEET WHICH
 COLLECTOR MODEL IS BEING INSTALLED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) SUBMIT TWO CCOPIES OF THE CURRENT SRCC/FSEC
 CERTIFICATION FOR THE COLLECTOR BEING INSTALLED.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) NOTE #6 ON THE DRAWING BY J.TORRES, ENGINEER, REFERS
 TO ECOSPARK INSTALLATION MANUAL.PLEASE SUBMIT TWO
 COPIES OF THIS MANUAL FOR REVIEW AND AS PART OF THIS
 PERRMIT.
 4) SUBMIT A PIPING DIAGRAM FOR THE PIPING TO BE
 INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1.
 5) WILL THERE BE A CONNECTION TO POTABLE WATER? IF SO,
 A BACKFLOW PREVENTER MAY REQUIRED TO ISOLATE THE
 HAZARD. 2014 FBC-PLUMBING SECS.608.1, 608.13.
 6) THE SYSTEM SHALL COMPLY WITH 2014 FBC-MECHANICAL
 SEC.1402.5.1 (PRESSURE & TEMPERATURE RELIEF VALVE).
 7) A VACUUM RELIEF MAY BE REQUIRED ON THE SYSTEM. 2014
 FBC-MECH. SEC.1402.5.2. CLARIFY.
 8) SHOW HOW PROTECTION FROM FREEZING WILL BE SUPPLIED.
 2014 FBC-MECH. SEC.1402.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  