| 2017-02-22 11:50:27 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING |
| | |
| | 1) PLEASE SEE BUILDING PLAN REVIEW FOR QUALITY OF PLAN |
| | AND NEEDED NOTES. |
| | |
| | 2) PLEASE PROVIDE NOTES TO DEMONSTARTE COMPLIANCE WITHT |
| | HE FOILLOWING FOR ALTERED ARES. |
| | |
| | FBCRE3703.2 KITCHEN AND DINING AREA RECEPTACLES. |
| | A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL |
| | BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, |
| | DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN |
| | COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF |
| | TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF |
| | WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER |
| | RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, |
| | BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS |
| | FOR REFRIGERATION APPLIANCES. |
| | |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | SHOW THE BELOW AS EXISTING, PROPOSED OR NOTE TO BE |
| | EVALUATED. |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| | FEET OF EACH SLEEPING ROOM. |
| | |
| | NOTE THAT A REVISED PANEL SCHEDULE WILL BE PROVIDED AS |
| | NEED OR INCLUDE IN RE-SUBMITTAL. |
| | |
| | |
| | |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |