| Date |
Text |
| 2017-02-22 11:05:35 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING ALTERATION LEVEL |
| | II |
| | |
| | 1) PLEASE INDICATE THE CODE IN EFFECT AND THE SCOPE OF |
| | WORK UPON THE PLAN AS FOLLOWS: |
| | FBC 2014 5TH ED. RESIDENTIAL |
| | FBC 2014 EXISTING BUILDING ALTERATION LEVEL II |
| | |
| | 2) THE DESIGNER IS REQUIRED TO SIGN THE PLAN PER |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 3) THE PRINT QUALITY OF THE PLAN IS TOO LIGHT, PLEASE |
| | REPRINT DARKER TO DEMONSTRATE THE ALTERATIONS PER FBC |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | |
| | 4) A DOOR AND GARAGE DOOR PRODUCT APPROVALS ARE |
| | PROVIDED. PLEASE INDICATE THE LOCATION OF THE DOOR TO |
| | BE REPLACED ACTUALLY ON THE PLAN AND NOTE UPON THE PLAN |
| | THE GARAGE DOOR REPLACEMENT. |
| | |
| | *NOTE THERE IS A SCOPE OF WORK PROVIDED INDICATING |
| | RELATED INFORMATION HOWEVER; THE ACTUAL PLAN SHOULD |
| | HAVE RELATIVE NOTATIONS AS IS DONE ON THE PLAN FOR |
| | WINDOW REPLACEMENTS. THERE ARE OTHER ITEMS IN THE SCOPE |
| | THAT SHOULD BE ADDED TO THE PLAN SUCH AS THE ADDING OF |
| | BEAMS, YOU MAY WISH TO CONSIDER ADDING THE SCOPE OF |
| | WORK NOTES IN GENERAL TO THE PLAN |
| | |
| | PLEASE ALSO NOTE THAT THE SCOPE OF WORK PROVIDED |
| | INDICATES OTHER WORK NOT SHOWN ON THE PLAN THAT EACH |
| | REQUIRE SEPARATE PERMITS AND PLAN SUBMITTALS IN THIS |
| | JURISDICTION AS FOLLOWS: |
| | A) POOL & POOL DECK MODIFICATIONS |
| | B) POOL BARRIER AND FENCE |
| | C) DRIVEWAY |
| | ADDITIONALLY NOTE THESE SEPARATE PERMIT SUBMITTALS WILL |
| | BE ASSESSED FEES BASED UPON THE VALUE OF EACH, |
| | ACCORDINGLY, YOU MAY WISH TO REDUCE THE VALUE CLAIMED |
| | ON THIS SUBMITTAL BY THE CORRESPONDING VALUE OF EACH TO |
| | BE SUBMITTED IN THE FUTURE. |
| | 5) PLEASE PROVIDE TYPICAL WALL SECTION DETAILS FOR NEW |
| | WALLS PARTICULARLY THE NEW SHOWER WALLS AND ANY SHOWER |
| | PAN DETAILS. |
| | 6) PLEASE INDICATE THAT REPLACEMENT BEDROOM WINDOWS |
| | WILL MEET THE REQUIREMENTS OF FBC EXISTING |
| | SECTION 704 MEANS OF EGRESS |
| | |
| | 704.1 GENERAL. |
| | MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 701.1 AND |
| | THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE. |
| | |
| | EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL |
| | DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5-PERCENT |
| | REDUCTION IN THE CLEAR OPENING DIMENSIONS OF |
| | REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED. |
| | |
| | 7) PLEASE PROVIDE NOTES TO DEMONSTRATE IN NEW BEDROOM |
| | NUMBER 4 THE EXISTING WINDOW WILL MEET THE REQUIREMENTS |
| | OF SECTION FBC-R310 EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |