| Date |
Text |
| 2017-03-20 14:17:48 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | THE BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | PROVISO MEANS THAT CONTRACTOR MAY BRING THE REQUIRED |
| | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES |
| | MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS |
| | PREFERRED AT THIS TIME OR IF RESUBMITTING REQUIRED |
| | INFORMATION PRIOR TO PERMIT ISSUANCE. |
| | |
| | |
| | 1- SIZE OF SECOND FLOOR FRAMING MEMBERS IS NOT CLEAR. |
| | SECOND FLOOR FRAMING PLAN ON SHEET A-1.0 CALLS FOR |
| | "2"X10" WOOD RAFTERS", WHILE OTHER SPECIFICATIONS ON |
| | THE SAME FRAMING PLAN AND DETAILS CALL FOR 2"X8" WOOD |
| | RAFTERS AND 2"X8" WOOD LEDGER. CLEARLY SPECIFY SIZE AND |
| | SPACING OF SECOND FLOOR FRAMING MEMBERS. AND, REVISE |
| | ALL DETAILS ON THE SAME PAGE TO MATCH SIZE. SEC. R301.1 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 2- INFORMATION ON PLANS IS NOT CLEAR. THE PROPOSED |
| | ADDITION IS ON THE SECOND FLOOR BUT ALL THE FLOOR PLANS |
| | ON SHEET A-1.0 AND A-1.1 REFER TO FIRST FLOOR. REVISE |
| | AS REQUIRED. CLEARLY IDENTIFY FLOOR WHERE WORK IS GOING |
| | TO BE PERFORMED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- SIZE OF HANGER SPECIFIED ON THE CONNECTOR |
| | SPECIFICATION SCHEDULE ON SHEET A-1.0 IS INCORRECT |
| | BASED ON THE FRAMING MEMBER SIZE. REVISE AS REQUIRED. |
| | COORDINATE WITH ITEM #1 ABOVE. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS |
| | BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". REVISE |
| | INFORMATION ON SHEET A-1.1 AS REQUIRED. |
| | |
| | 5- GENERAL NOTES ON SHEET A-1.1 REFERENCE THE 2010 FBC. |
| | THE CURRENT CODE IS THE 2014 FBC, 5TH EDITION. REVISE |
| | ALL THE NOTES THAT REFERENCE THE 2010 CODE AS REQUIRED. |
| | CHAPTER 553 FLORIDA STATUTE. |
| | |
| | 6- PROPERTY IS LOCATED IN FLOOD ZONE A5. NEED ELEVATION |
| | CERTIFICATE SHOWING FINISH FLOOR ELEVATION OF MAIN |
| | HOUSE AND GARAGE. IF GARAGE FINISH FLOOR ELEVATION IS |
| | BELOW THE REQUIRED FINISHED FLOOR ELEVATION, THEN FLOOD |
| | VENTS MAY BE REQUIRED. |
| | |
| | 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISE SHEET AND REMOVE OLD SHEET. |
| | DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS FOR |
| | REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS , PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| 2017-03-17 15:09:13 | 03/20/17 FLOOD ZONE A5. ASKED ROBERT BROWN ABOUT |
| | ELEVATION CERTIFICATE. HE AGREED TO ASK FOR IT FOR OUR |
| | RECORDS TO VERIFY FINISH FLOOR ELEVATION. |
| | |
| | |