| 2017-02-27 10:27:11 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES |
| | 2 AND 3 IS INCORRECT. THE SPACING FOR ZONE 2 SHOULD BE |
| | 8" OC IN THE LAP AND 8" OC IN 3 ROWS IN THE FIELD. THE |
| | SPACING FOR ZONE 3 SHOULD BE 5" OC IN THE LAP AND 5" OC |
| | IN 3 ROWS IN THE FIELD. IT APPEARS THAT THE FRACTIONS |
| | WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED BY RAS |
| | 117. ALSO, PLEASE SUBMIT THE ACTUAL RAS 117 ENHANCED |
| | FASTENING CALCULATIONS WITH YOUR DOCUMENTS. GENERAL |
| | LIMITATION NUMBER 7 ON PAGE 16 OF NOA NO. 13-1022.15 |
| | REQUIRES ROOFING APPLICATION STANDARD 117 CALCULATIONS |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED ARCHITECT OR |
| | REGISTERED ROOF CONSULTANT. SEE FBC 107.2.1.3 |
| | ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE |
| | DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA |
| | NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION |
| | AND THE BASIS OF CALCULATIONS. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE |
| | BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR |
| | ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL, |
| | SIGNATURE AND DATE AS STATE LAW REQUIRES. |
| | |