2017-02-27 10:27:11PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES
 2 AND 3 IS INCORRECT. THE SPACING FOR ZONE 2 SHOULD BE
 8" OC IN THE LAP AND 8" OC IN 3 ROWS IN THE FIELD. THE
 SPACING FOR ZONE 3 SHOULD BE 5" OC IN THE LAP AND 5" OC
 IN 3 ROWS IN THE FIELD. IT APPEARS THAT THE FRACTIONS
 WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED BY RAS
 117. ALSO, PLEASE SUBMIT THE ACTUAL RAS 117 ENHANCED
 FASTENING CALCULATIONS WITH YOUR DOCUMENTS. GENERAL
 LIMITATION NUMBER 7 ON PAGE 16 OF NOA NO. 13-1022.15
 REQUIRES ROOFING APPLICATION STANDARD 117 CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT OR
 REGISTERED ROOF CONSULTANT. SEE FBC 107.2.1.3
 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE
 BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR
 ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE AS STATE LAW REQUIRES.
  