Plan Review Notes
Plan Review Notes For Permit 17020392
Permit Number 17020392
Review Stop B
Sequence Number 1
Notes
Date Text
2017-02-13 17:35:05PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESIGNER OF RECORD'S REVIEW STAMPS ARE REQUIRED
 ON THE PRODUCT APPROVALS, NOT THE ENHANCED FASTENING
 CALCULATIONS. FBC 107.3.4
  
 2) THE RAS 117 ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 471 &
 FAC 61G15 - 23.002
  
 3) THE ROOF ZONE WIND PRESSURE CALCULATIONS FOR THE 10
 FT. MEAN ROOF HEIGHT IS NOT APPLICABLE TO BUILDING "A".
 THESE 3 STORY TOWNHOUSES DO NOT HAVE THE DETACHED
 GARAGE. PLEASE REMOVE THEM FROM THIS SUBMITTAL. FBC
 107.2.1
  
 4) THE ROOF ZONE WIND PRESSURE CALCULATION DOCUMENTS
 THAT WERE SUBMITTED, SPECIFY A 160 MPH BASIC WIND
 SPEED, A 30 FT MEAN ROOF HEIGHT AND EXPOSURE CATEGORY
 D. ON SHEET S15 OF THE APPROVED PLANS A 170 MPH BASIC
 WIND SPEED, A 33.33 FT MEAN ROOF HEIGHT AND EXPOSURE
 CATEGORY C ARE SPECIFIED. PLEASE CORRECT THE ROOF ZONE
 WIND PRESSURE CALCULATION DATA TO CORRESPOND WITH THE
 APPROVED PLANS. FBC 107.2.1 & FBC-R301.2.1
  
 5) THE FINAL BASE SHEET FASTENER SPACING FOR ROOF ZONES
 2 AND 3 IS INCORRECT. THE SPACING SHOULD BE 8" OC IN
 THE LAP AND 3 FIELD ROWS FOR ZONE 2 AND 5" OC IN THE
 LAP AND 3 FIELD ROWS FOR ZONE 3. IT APPEARS THAT THE
 FRACTIONS WERE ROUNDED UP RATHER THAN DOWN AS REQUIRED
 BY RAS 117. ALSO, PLEASE SHOW THE ACTUAL RAS 117
 CALCULATIONS ON YOUR DOCUMENTS. FBC 107.2.1.4
  