Plan Review Notes
Plan Review Notes For Permit 17020365
Permit Number 17020365
Review Stop G
Sequence Number 1
Notes
Date Text
2017-02-14 05:08:241) SHOW THE APPROXIMATE BTU LOAD FOR THE FUTURE POOL
 HEATER TO ENSURE THAT THE SYSTEM IS SIZED CORRECTLY . A
 COMPREHENSIVE REVIEW CANNOT BE DONE WITHOUT IT.2014 FGC
 SEC.402.2.
 2) THE LINE FOR THE FUTURE POOL HEATER SHALL BE
 EQUIPPED WITH A SHUTOFF VALVE, REGULATOR, NIPPLE AND
 CAP TO ENSURE THE SAFETY AND INTEGRITY OF THE SYSTEM.
 3) SHOW THE TYPE OF PIPE AND THE SIZE OF THE STUB OUT
 PIPING COMING OFF THE STEP-DOWN REGULATOR ALL
 APPLIANCES.
 4) SHOW THE CORRESPONDING EHD FOR THE CSST ON THE PLAN.
 COMPLY WITH TABLE 402.4 (15).
 5) SHOW THE DISTANCE OF THE TANKLESS WATER HEATERS FROM
 OPERABLE DOORS AND WINDOWS ON THE SITE PLAN. THE
 TANKLESS WATER HEATERS SHALL BE LOCATED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 NOTE: FOR ALL GAS PERMITS: IF COMBUSTION AIR
 CALCULATIONS ARE REQUIRED THEY SHALL BE SUBMITTED ALONG
 WITH THE OTHER PERMIT DOCUMENTS AT THE TIME OF PERMIT
 APPLICATION SUBMITTAL. THE GAS INSTALLATION SHALL MEET
 ALL THE REQUIREMENTS OF THE FUEL GAS CODE AND THIS
 INCLUDES COMBUSTION AIR CALCULATIONS. THE NOTE ON THE
 PLANS THAT READS " MAKE-UP AIR BY OTHERS" WILL RESULT
 IN A FAILED PLAN REVIEW IF COMBUSTION AIR CALCULATIONS
 ARE REQUIRED AND NOT SUBMITTED.
  