| Plan Review Notes For Permit 17020362 |
| Permit Number |
17020362 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-14 11:42:04 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020362 | | | 2/14/17 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) M2.1: THE NEW FPT-11-12 APPEARS TO BE SUPPLYING 1400 | | | CFMS OF AIR, HOWEVER THE SCHEDULE ON M4.1 INDICATES A | | | DESIGN AIRFLOW OF 900 CFMS- PLEASE CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|