2018-01-04 11:07:36MECHANICAL PROVISOS
 1/4/18
  
 1) REVISION REQUIRED TO RELOCATE OUTSIDE AIR INTAKES
 MINIMUM 10' FROM ADJACENT BUILDING.
  
 2) SEPARATE PERMITS REQUIRED FOR KITCHEN EXHAUST HOOD,
 FIRE SUPPRESSION SYSTEM,
  
 & WALK-IN COOLER. NOTE: ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR HOOD EXHAUST AND SUPPLY DUCTWORK.
  
  
 DEFERRED SUBMITTALS:
  
 1) ROOFTOP AC CONDENSER AND STAND ENGINEERING AND NOA
  
 2) OUTSIDE AIR INTAKE LOUVER NOA
  
 3) ROOF LADDER CONSTRUCTION DETAILS
  
 ENGINEERING FOR INSTALLATION OF THE EXTERIOR HOOD
 EXHAUST AND SUPPLY DUCTWORK
  