| Notes |
| Date |
Text |
| 2018-01-04 11:07:36 | MECHANICAL PROVISOS | | | 1/4/18 | | | | | | 1) REVISION REQUIRED TO RELOCATE OUTSIDE AIR INTAKES | | | MINIMUM 10' FROM ADJACENT BUILDING. | | | | | | 2) SEPARATE PERMITS REQUIRED FOR KITCHEN EXHAUST HOOD, | | | FIRE SUPPRESSION SYSTEM, | | | | | | & WALK-IN COOLER. NOTE: ENGINEERING FOR INSTALLATION OF | | | THE EXTERIOR HOOD EXHAUST AND SUPPLY DUCTWORK. | | | | | | | | | DEFERRED SUBMITTALS: | | | | | | 1) ROOFTOP AC CONDENSER AND STAND ENGINEERING AND NOA | | | | | | 2) OUTSIDE AIR INTAKE LOUVER NOA | | | | | | 3) ROOF LADDER CONSTRUCTION DETAILS | | | | | | ENGINEERING FOR INSTALLATION OF THE EXTERIOR HOOD | | | EXHAUST AND SUPPLY DUCTWORK | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | |
|