| 2017-11-30 10:25:27 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17020359 |
| | 11/30/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | A) SOME OF THE COMMENTS FROM THE PREVIOUS REVIEW STILL |
| | EXIST. I HAVE REPRINTED THOSE BELOW- PLEASE COMPLY. |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. NO |
| | CHANGES TO THE O/A CALCULATION SCHEDULE HAVE BEEN MADE- |
| | SEE SHEET M0.1. ( PLEASE NOTE THAT THE OUTDOOR AIR RATE |
| | FOR DINING ROOMS IS BASED ON AN OCCUPANT LOAD OF 70 |
| | PERSONS PER 1000 SQ. FT- PLEASE REVISE THE CALCULATION |
| | USING THE CORRECT NUMBERS OF PERSONS.) |
| | |
| | 2) COMMENT 4 FROM THE 1ST REVIEW STILL EXISTS: THE O/A |
| | INTAKE OPENINGS FOR THE AHU'S ARE NOT LOCATED A MINIMUM |
| | OF 10' AWAY FROM THE ADJACENT BUILDING. THIS INCLUDES |
| | AHU-1, AHU-2, AHU-1A & AHU- 1B. |
| | |
| | 4) SUBMIT TWO COPIES OF NOA #16- 0601.01 WITH ALL |
| | APPLICABLES NOTES, ASSEMBLY AND INSTALLATION DETAILS, |
| | AND DESIGN PRESSURES ETC. EITHER CIRCLED, HIGHLIGHTED, |
| | OR OTHERWISE MARKED BY THE ENGINEER OF RECORD. |
| | |
| | 5) SHOW THE LOCATION OF THE DRYER DUCT CHASE ON THE |
| | FLOOR PLAN AND PROVIDE A CLEANOUT PER SECTION 504.3. |
| | |
| | 6) PROVIDE STRUCTURAL DETAILS FOR ATTACHING THE MUA |
| | DUCTWORK TO THE SIDE OF THE BUILDING- SECTION 301.15. |
| | |
| | B) M1.1: IT APPEARS THAT AHU-1 IS BEING INSTALLED ABOVE |
| | THE WALK-IN COOLER BOX WHICH WILL RESTRICT ACCESS TO |
| | THE UNIT DESPITE THE ACCESS PANEL LOCATED IN THE |
| | CEILING ABOVE THE BOX. SEE SHEET A-102D. |
| | |
| | C) SHEET A507D WHICH IS SUPPOSED TO PROVIDE ROOF LADDER |
| | CONSTRUCTION DETAILS IS MISSING FROM THE PLAN SETS. |
| | PLEASE SEE SHEET A-101D, FLOOR PLAN NOTE #1 WHICH IS |
| | IDENTIFYING THE ROOF LADDER AND REFERRING TO THE PLAN |
| | SHEET. |
| | |
| | D) PLEASE PROVIDE A PLAN INDEX. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |