Plan Review Notes
Plan Review Notes For Permit 17020359
Permit Number 17020359
Review Stop B
Sequence Number 3
Notes
Date Text
2017-12-08 14:04:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020359
 ADD: 518 S. DIXIE HWY. (1ST FLOOR BUILD-OUT)
 CONT: TBD
 TEL: 954-570-9500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. DEC. 08/2017
 ACTION: DENIED
  
 1) A E-MAIL WAS SUBMITTED FROM BRIAN BULLOCK ON
 12/05/2017 THAT WAS ASKING ABOUT FIRE RATINGS OF
 PRIMARY STRUCTURAL MEMBERS, ENCASED IN A FLOOR CEILING
 ASSEMBLY, BEAMS BENEATH THE FIRE RATED FLOOR CEILING
 ASSEMBLY, RATING OF COLUMNS CARRYING THE 2ND FLOOR
 LOADS.
  
 PLEASE SEE THE RESPONSE SENT ON 12/06/2017:
  
 I BELIVE YOU ARE REFERRING TO TABLE 601 OF THE 2014
 FBC-B WITH BUILDING TYPE VB CONSTRUCTION. YOU REFERENCE
 THAT YOU ARE CREATING A HORIZONTAL FIRE BARRIER BETWEEN
 THE UPSTAIRS R2 OCCUPANCY AND THE 1ST FLOOR MERCANTILE
 WHICH IS REQUIRED BY TABLE 707.3.10.
 THE FLOOR/ CEILING ASSEMBLY IS TO MAKE A 2 HOUR FIRE
 BARRIER FROM THE EXTERIOR WALL TO EXTERIOR WALL, THE
 EXTERIOR BEARING WALLS WILL MAKE THE 2 HOUR FIRE RATING
 WITH THE BLOCK WORK STUCCO ON THE EXTERIOR AND DRYWALL
 ON THE INTERIOR. THE EXTERIOR DOORS DO NOT NEED TO BE
 FIRE RATED UNLESS BY REQUIREMENTS FOUND IN TABLE 705.8.
  
 IF THERE ARE COLUMNS AND OR PRIMARY FRAMING MEMBERS
 BELOW THE 2 HOUR HORIZONTAL FIRE BARRIER THEN THEY ARE
 TO BE FIRE RATED THE SAME AMOUNT OF TIME. THE PRIMARY
 FRAMING MEMBERS CANNOT FAIL BEFORE THE 2 HOUR FLOOR
 CEILING ASSEMBLY, OTHERWISE THE FLOOR ASSEMBLY WOULD
 COLLAPSE. PLEASE SEE THE DEFINITION OF PRIMARY
 STRUCTURAL FRAME.
  
 PRIMARY STRUCTURAL FRAME. THE PRIMARY STRUCTURAL FRAME
 SHALL INCLUDE ALL OF THE FOLLOWING STRUCTURAL MEMBERS:
  
 1. THE COLUMNS;
  
 2. STRUCTURAL MEMBERS HAVING DIRECT CONNECTIONS TO THE
 COLUMNS, INCLUDING GIRDERS, BEAMS, TRUSSES AND
 SPANDRELS;
  
 3. MEMBERS OF THE FLOOR CONSTRUCTION AND ROOF
 CONSTRUCTION HAVING DIRECT CONNECTIONS TO THE COLUMNS;
 AND
  
 4. BRACING MEMBERS THAT ARE ESSENTIAL TO THE VERTICAL
 STABILITY OF THE PRIMARY STRUCTURAL FRAME UNDER GRAVITY
 LOADING SHALL BE CONSIDERED PART OF THE PRIMARY
 STRUCTURAL FRAME WHETHER OR NOT THE BRACING MEMBER
 CARRIES GRAVITY LOADS.
  
 707.5 CONTINUITY.
 FIRE BARRIERS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE AND SHALL BE SECURELY ATTACHED THERETO. SUCH FIRE
 BARRIERS SHALL BE CONTINUOUS THROUGH CONCEALED SPACE,
 SUCH AS THE SPACE ABOVE A SUSPENDED CEILING. JOINTS AND
 VOIDS AT INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8
 AND 707.9
  
 707.5.1 SUPPORTING CONSTRUCTION.
 THE SUPPORTING CONSTRUCTION FOR A FIRE BARRIER SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE FIRE BARRIER SUPPORTED. HOLLOW VERTICAL SPACES
 WITHIN A FIRE BARRIER SHALL BE FIREBLOCKED IN
 ACCORDANCE WITH SECTION 718.2 AT EVERY FLOOR LEVEL.
  
 1012.5.1.1 FIRE WALL ALTERNATIVE. 3. THE
 FIRE-RESISTANCE RATING OF THE FIRE BARRIERS AND
 HORIZONTAL ASSEMBLIES SHALL NOT BE LESS THAN THAT
 SPECIFIED FOR FIRE WALLS IN TABLE 706.4 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 EXCEPTION: WHERE HORIZONTAL ASSEMBLIES ARE USED TO
 LIMIT THE MAXIMUM ALLOWABLE AREA, THE REQUIRED
 FIRE-RESISTANCE RATING OF THE HORIZONTAL ASSEMBLIES
 SHALL BE PERMITTED TO BE REDUCED BY 1 HOUR PROVIDED THE
 HEIGHT AND NUMBER OF STORIES INCREASES ALLOWED FOR AN
 AUTOMATIC SPRINKLER SYSTEM BY SECTION 504.2 OF THE
 FLORIDA BUILDING CODE, BUILDING ARE NOT USED FOR THE
 BUILDINGS.
  
 I BELIEVE THE DESIGNER OF RECORD HAS NOT USED THE AREA
 INCREASE IN HEIGHT OR AREA FOR FIRE SPRINKLERS, IT
 WOULD HAVE TO BE VERIFIED THE FIRE SPRINKLER SYSTEM IS
 A FULL NFPA 23 SYSTEM, NOT A 13R, IF THE NFPA 13 FIRE
 SPRINKLER IS INSTALLED THEN THE 1 HOUR REDUCTION CAN
 OCCUR TO THE FLOOR / CEILING ASSEMBLY AS WELL AS THE
 PRIMARY FRAMING MEMBERS AND COLUMNS TO ONE HOUR FIRE
 RESISTANCE RATING.
  
 SHEET A001D INDICATES THE BUILDING TO HAVE A NEW FIRE
 SPRINKLER SYSTEM, THE TYPE OF SYSTEM IS NOT DECLARED?
 SHEET A-102D THE REFLECTIVE CEILING PLAN INDICATES
 DROPPED SECTIONS FOR STEEL BEAMS BUT THE PLANS DO NOT
 INDICATE HOW THE PRIMARY FRAMING (STRUCTURAL) MEMBERS
 ARE TO BE FIRE RATED?
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  