Plan Review Notes
Plan Review Notes For Permit 17020359
Permit Number 17020359
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-09 14:41:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020539
 8/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. NO
 CHANGES TO THE O/A CALCULATION SCHEDULE HAVE BEEN MADE-
 SEE SHEET M0.1
  
 2) COMMENT 4 FROM THE 1ST REVIEW STILL EXISTS: THE O/A
 INTAKE OPENING FOR AHU-1 IS NOT LOCATED A MINIMUM OF
 10' AWAY FROM THE ADJACENT BUILDING.
  
 3) COMMENT 6 FROM THE 1ST REVIEW STILL EXISTS: SHOW THE
 LOCATION OF KEYNOTE #3 (THE REMOVABLE ACCESS PANEL FOR
 AHU-1).
  
 4) SUBMIT TWO COPIES OF NOA #16- 0601.01 WITH ALL
 APPLICABLES NOTES, ASSEMBLY AND INSTALLATION DETAILS,
 AND DESIGN PRESSURES ETC. EITHER CIRCLED, HIGHLIGHTED,
 OR OTHERWISE MARKED BY THE ENGINEER OF RECOR
  
 5) SHOW THE LOCATION OF THE DRYER DUCT CHASE ON THE
 FLOOR PLAN AND PROVIDE A CLEANOUT PER SECTION 504.3.
  
 6) PROVIDE STRUCTURAL DETAILS FOR ATTACHING THE MUA
 DUCTWORK TO THE SIDE OF THE BUILDING- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  