| Notes |
| Date |
Text |
| 2017-08-09 14:41:07 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020539 | | | 8/9/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS. NO | | | CHANGES TO THE O/A CALCULATION SCHEDULE HAVE BEEN MADE- | | | SEE SHEET M0.1 | | | | | | 2) COMMENT 4 FROM THE 1ST REVIEW STILL EXISTS: THE O/A | | | INTAKE OPENING FOR AHU-1 IS NOT LOCATED A MINIMUM OF | | | 10' AWAY FROM THE ADJACENT BUILDING. | | | | | | 3) COMMENT 6 FROM THE 1ST REVIEW STILL EXISTS: SHOW THE | | | LOCATION OF KEYNOTE #3 (THE REMOVABLE ACCESS PANEL FOR | | | AHU-1). | | | | | | 4) SUBMIT TWO COPIES OF NOA #16- 0601.01 WITH ALL | | | APPLICABLES NOTES, ASSEMBLY AND INSTALLATION DETAILS, | | | AND DESIGN PRESSURES ETC. EITHER CIRCLED, HIGHLIGHTED, | | | OR OTHERWISE MARKED BY THE ENGINEER OF RECOR | | | | | | 5) SHOW THE LOCATION OF THE DRYER DUCT CHASE ON THE | | | FLOOR PLAN AND PROVIDE A CLEANOUT PER SECTION 504.3. | | | | | | 6) PROVIDE STRUCTURAL DETAILS FOR ATTACHING THE MUA | | | DUCTWORK TO THE SIDE OF THE BUILDING- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|