2017-02-10 15:32:211ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020359
 2/10/17
  
 1) SHEET M0.1: PLEASE CORRECT THE O/A CALCULATION FOR
 THE DINING ROOM TO THE REQUIREMENTS OF TABLE 403.3, AND
 NOT TO THE ARCHITECTURAL SEATING LAYOUT WHICH IS NOT
 SHOWN ON THE ARCHITECTURAL SHEETS.
  
 2) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN EXHAUST
 HOODS, FIRE SUPPRESSION, AND WALK-IN COOLERS AND
 FREEZERS. PLEASE PLACE A NOTE ON THE ACCORDINGLY.
  
 3) M1.1: PLEASE ENLARGE THE PRINT IDENTIFYING THE
 DIMENSIONS OF KITCHEN HOOD EXHAUST AND SUPPLY DUCTWORK,
 AND INLET AND OUT SIZES. PLEASE NOTE THAT ADDITIONAL
 COMMENTS REGARDING THE KITCHEN EXHAUST HOODS, THE
 EXISTING EXHAUST RISER, ETC. MAY OCCUR WHEN SEPARATE
 PLANS ARE SUBMITTED FOR REVIEW.
  
 4) M1.1: THE O/A INLETS (KEYNOTES 3 & 4) CANNOT BE
 LOCATED WITHIN 10' OF LOT LINES OR BUILDINGS ON THE
 SAME LOT- SECTION 401.4. PLEASE RELOCATE THE INLETS AND
 PROVIDE LOUVERS TO PROTECT THE OPENINGS IF THE INLETS
 ARE TO BE RELOCATED TO OTHER EXTERIOR WALL LOCATIONS-
 SEE SECTION 401.5 AND SUBMIT A FLORIDA PRODUCT APPROVAL
 AND/OR A MIAMI-DADE NOA FOR THE LOUVERS.
  
 5) M1.1: REFER TO SECTION C403.2.4.4 FBC-14 ENEREGY
 CONSERVATION AND PROVIDE DAMPERS FOR THE O/A DUCTS THAT
 WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES ARE
 NOT IN USE.
  
 6) M1.1: THE PLAN APPEARS TO INDICATE THAT ACCESS FOR
 MAINTENANCE AND REPLACEMENT OF AHU-1 WILL BE OBSTRUCTED
 BY THE WALK-IN COOLER- SEE SECTION 306.1 AND RELOCATE
 IT TO AN ACCESSIBLE LOCATION.
  
 7) M0.1: PROVIDE SIZES FOR THE B & C DIFFUSERS, AND THE
 D RETURN GRILLES SHOWN IN THE SCHEDULE.
  
 8) M0.2: SUBMIT TWO COPIES OF NOA #13-1017.09 WITH ALL
 APPLICABLES NOTES, ASSEMBLY AND INSTALLATION DETAILS,
 AND DESIGN PRESSURES ETC. EITHER CIRCLED, HIGHLIGHTED,
 OR OTHERWISE MARKED BY THE ENGINEER OF RECORD.
  
 9) M1.2: THE PLAN SHOWS A MAKEUP AIR DUCT FOR A DRYER,
 HOWEVER NO DRYER IS SHOWN IN THE PROPOSED RESTAURANT-
 PLEASE CLARIFY AND NOTE THAT WIND LOAD ENGINEERING IS
 REQUIRED FOR TIE DOWN OF THE DUCT TO THE ROOF
 STRUCTURE- SECTION 301.15.
  