| Plan Review Notes For Permit 17020359 |
| Permit Number |
17020359 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-21 10:47:52 | 518 SOUTH DIXIE HIGHWAY | | | PERMIT #17020359 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW | | | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE | | | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE | | | ORDERED FROM WWW.KNOXBOX.COM | | | | | | SHEET A-001D/A-106D/FP1.1: ARCHITECTURAL SHEETS | | | INDICATE FIRE SPRINKLERS WILL ONLY BE PROTECTING THE | | | SECOND FLOOR; HOWEVER, THE FIRE PROTECTION DRAWING | | | INDICATES BOTH FLOORS WILL BE PROTECTED. | | | | | | SHEET A-106D: ADD INTENDED SEATING PLAN TO THE LIFE | | | SAFETY PLAN. | | | | | | SHEET A-106D: SOUTHWEST EGRESS DOORS (DOUBLE DOORS) ARE | | | SWINGING AGAINST THE FLOW OF EGRESS. PER NFPA 101 | | | SECTION 7.2.1.4.2, DOORS SERVING AN OCCUPANT LOAD OF 50 | | | OR MORE PERSONS SHALL SWING IN THE DIRECTION OF EGRESS. | | | | | | SHEET FP1.1: THE ARCHITECTURAL PLANS INDICATE THIS IS | | | PRIMARILY A MERCANTILE OCCUPANCY. A SPRINKLER SYSTEM | | | DESIGNED FOR ORDINARY HAZARD MAY BE MORE APPROPRIATE. | | | | | | SHEET FP1.1: NO CIVIL PLANS SUBMITTED SHOWING THE | | | INCOMING FIRE MAIN AND FIRE DEPARTMENT CONNECTION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|