Plan Review Notes
Plan Review Notes For Permit 17020359
Permit Number 17020359
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-02 08:22:081ST ELECTRICAL REVEIW JAKE LEAHY 2/28/17
  
 1) E.02 PHASE 1 RISER DIAGRAM:
  
 A) NEED LOAD CALCULATION FOR THE 225A MAIN AND HOW IT
 WAS FIGURED. PER 220
 B) PANEL SCHEDULES FOR PANELS "A", "B", "C" 408.4(A)
 C) INTERSYSTEM BONDING TERMINATION REQUIRED AT SERVICE
 250.94
 D) COMMON GORUNDING ELECTRODE REQUIRED 250.58
  
 2) E.02 PHASE 2 RISER DIAGRAM:
  
 A) MAIN DISCONNECT FUSED AT 600A? 230.90(A), 230.91
 B) LOAD CALCULATION FOR THE 600A MAIN PER 220
 C) INTERSYSTEM BONDING TERMINATION REQUIRED AT SERVICE
 250.94
 D) PANEL SCHEDULES 408.4(A)(B)
  
 3) PAGE E1.1:
  
 A) OUTLETS UNDER BAR TO SHALL BE GFCI PROTECTED IF
 WITHIN 6' OF A SINK 210.8(B)(5)
 B) USB OUTLET RECEPTACLES SHALL BE LISTED 110.3(A)(B)
  
 4) PAGE E1.2:
  
 A) LIGHTING POWER ALLOWANCES FOR SPACE ARE REQUIRED PER
 FBC EC C405.5.2
  