2017-02-27 09:26:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020359
 ADD: 518 S. DIXIE HWY. (1ST FLOOR BUILD-OUT)
 CONT: TBD
 TEL: 954-570-9500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 24/2017
 ACTION: DENIED
  
 1) SHEETS A-101D & A-106D THE LIFE SAFETY PLAN SHOWS
 THE 1ST FLOOR AS A MERCANTILE OCCUPANCY OF
 APPROXIMATELY 3,598 SQUARE FEET / 30 SQ. FT. PER
 OCCUPANT = 117 THE OCCUPANT LOAD. WITH THE BREAK OUT
 AREA OF THE KITCHEN AND COFFEE BAR AREA THE OCCUPANT
 LOAD IS REDUCED DRAMATICALLY BUT STILL OVER 50
 OCCUPANTS.
 THE PAIR OF DOORS THAT FACE DIXIE HWY WILL NEED TO BE A
 PAIR OF OUTSWING DOORS BUT NOT CROSS OVER THE PROPERTY
 LINE. THIS SPACE WAS BROKEN UP INTO 3 TENANT SPACES
 WHERE THE OCCUPANT LOAD WAS NOT AS HIGH.
  
 2014 FBC-B 1008.1.2 DOOR SWING. (9) DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM
 OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS.
  
 2014 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2) THE LIFE SAFETY PLAN A-106D SHOWS AN OUTSIDE AREA A
 DINING GARDEN WITH AN OCCUPANT LOAD OF 28 OCCUPANTS.
 THE LAYOUT OF THE TABLES AND CHAIRS FOR DINING IS NOT
 SHOWN ON THE LIFE SAFETY PLAN PLEASE SHOW THE SEATING
 ARRANGEMENT FOR MEANS OF EGRESS SHOW COMPLIANCE WITH
 FBC-B 1017.5 AISLES IN OTHER THAN ASSEMBLY SPACES AND
 GROUPS B AND M. PLEASE NOTE WHEN THE OCCUPANT LOADS FOR
 DINING MAY BE A A2 USAGE THE OCCUPANCY TYPE IS
 CONSIDERED BUSINESS NOT ASSEMBLY. FBC-B 303.1.2 SMALL
 ASSEMBLY SPACES.
 2. A ROOM OR SPACE USED FOR ASSEMBLY PURPOSES THAT IS
 LESS THAN 750 SQUARE FEET (70 M2) IN AREA AND ACCESSORY
 TO ANOTHER OCCUPANCY SHALL BE CLASSIFIED AS A GROUP B
 OCCUPANCY OR AS PART OF THAT OCCUPANCY.
  
 3) ON THE LIFE SAFETY PLAN A-106D PLEASE PROVIDE THE
 DIMENSIONS BETWEEN THE (2) BUILDING AND ALSO PROVIDE
 THE DIMENSION BETWEEN THE TAYLOR SHOP AND THE ADJACENT
 PROPERTY LINE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3A) ON THE LIFE SAFETY PLAN A-106D PLEASE NOTE THERE IS
 NO DOOR & GATE SCHEDULE FOUND WITHIN THE SET OF PLANS,
 PLEASE PROVIDE A DOOR & GATE SCHEDULE AND NOTE THE
 REQUIREMENT FOR PANIC AND FIRE EXIT HARDWARE. 2014
 008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS AND OR GATES SERVING ROOMS OR SPACES WITH AN
 OCCUPANT LOAD OF 50 SHALL NOT BE PROVIDED WITH A LATCH
 OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 3B) ON THE LIFE SAFETY PLAN A-106D. THE (2) SINGLE REAR
 EXIT DOORS SHOWN DOES NOT SHOW THE DIMENSION BETWEEN
 THE 2 BUILDINGS MAY NOT COMPLY WITH SECTION 1005.7.1
 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN
 ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN ONE-HALF. WITH OCCUPANT LOADS OF 50 OR MORE
 THE REQUIRED EGRESS WIDTH OF 44 INCHES IS REQUIRED, ?
 OF THAT DIMENSION WOULD BE 22 INCHES.
  
 4) ON THE LIFE SAFETY PLAN A-106D. THE 7 FOOT HIGH
 PRE-CAST PROPERTY LINE WILL REQUIRE A SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES. 2014 FLORIDA BUILDING CODE
 W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 105.1 A PERMIT
 IS REQUIRED.
  
 5) ON THE LIFE SAFETY PLAN A-106D. FBC-B 1027.4.2
 CONSTRUCTION AND OPENINGS. WHERE AN EGRESS COURT
 SERVING A BUILDING OR PORTION THEREOF IS LESS THAN 10
 FEET (3048 MM) IN WIDTH, THE EGRESS COURT WALLS SHALL
 HAVE NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED
 CONSTRUCTION FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE
 THE FLOOR OF THE COURT. OPENINGS WITHIN SUCH WALLS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 3/4 HOUR.
  
 6) ON THE LIFE SAFETY PLAN A-106D. THE WAY THE 2ND
 STORY STAIRWELL APPEARS TO BE COMING OUT OF A 2 STORY
 TAYLOR SHOP AND EXITING THE STAIR ON A LANDING BETWEEN
 THE 2 BUILDING AND STILL TRAVELING DOWN 4 RISERS TO
 GRADE, WE KNOW THAT IS NOT THE INTENT BUT THE DEPICTION
 OF THE STAIRS SHOULD SHOW THE HIDDEN LINES OF THE 2ND
 STORY PORTION OF THE STAIR AND ENCLOSURE. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) ON THE LIFE SAFETY PLAN A-106D. PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING 2014 FBC- ACCESSIBILITY
 REQUIREMENTS:
 7A) 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS
 AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR
 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTER TOP
 SHALL EXTEND THE SAME DEPTH AS THE SALES OR SERVICE
 COUNTER TOP.
 ACCESS. CODE 227.1. WHERE PROVIDED, CHECK-OUT AISLES,
 SALES COUNTERS, SERVICE COUNTERS, FOOD SERVICE LINES,
 QUEUES, AND WAITING LINES SHALL COMPLY WITH 227 AND
 904.
  
 7B) ACCESS. CODE 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
  
  
 7B)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 7B)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 7B)(3) 226 DINING SURFACES AND WORK SURFACES. 226.1.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902. IN ADDITION, WHERE WORK SURFACES ARE
 PROVIDED FOR USE BY OTHER THAN EMPLOYEES, AT LEAST 5
 PERCENT SHALL COMPLY WITH 902.
  
 8A) ON THE LIFE SAFETY PLAN A-106D. THE PLANS DO NOT
 INDICATE HOW MANY OF THE ENTRANCE/ EXITS ARE FLUSH OR
 WITHIN ? INCH OF THE FINISH INTERIOR FLOOR. ACCESS.
 CODE 206.2.4 SPACES AND ELEMENTS. AT LEAST ONE
 ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY WHICH ARE
 OTHERWISE CONNECTED BY A CIRCULATION PATH UNLESS
 EXEMPTED BY 206.2.3 EXCEPTIONS 1 THROUGH 7.
 8B) ON THE LIFE SAFETY PLAN A-106D. ACCESS. CODE
 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
  
 9A) SHEET A-501 D DETAIL #9 SHOWS BRAILLE ON A SIGN AND
 THE HEIGHT OF THE BRAILLE IS 5 FOOT ABOVE FINISHED
 FLOOR. NOTE, THIS IS ABOVE REACH RANGES. SEE
 ACCESSIBILITY 308.2 FORWARD REACH & 308.3 SIDE REACH.
 703.4.1 HEIGHT ABOVE FINISH FLOOR OR GROUND. TACTILE
 CHARACTERS (BRAILLE) ON SIGNS SHALL BE LOCATED 48
 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 9B) SHEET A-501 D DETAIL #2 SHOWS THE GRAB RAILS FOR
 THE WATER CLOSET TO BE MEASURED FROM FLOOR CENTERLINED
 ABOVE THE FLOOR. IN THE 2014 FBC-ACCESS. CODE IN
 SECTION 609.4 THE MEASUREMENTS ARE NO LONGER CENTER
 LINED BUT TAKEN FROM THE TOP OF THE GRASPING SURFACE.
 ACCESS. CODE 609.4.
  
 10) THE COVERSHEET A-001D INDICATES THE SECOND FLOOR IS
 TO HAVE FIRE SPRINKLERS THROUGHOUT THE SECOND FLOOR AND
 STAIRS ONLY WHEREAS THE FLOOR PLAN FP1.1 SHOWS A FIRE
 SPRINKLER LAYOUT FOR THE 1ST FLOOR ONLY.
  
 11A) SHEET A-102D THE 1ST FLOOR LIFE SAFETY PLAN SHOWS
 AREA OF THE 1ST FLOOR WITH 2 LAYERS OF 5/8 GYPSUM.
 THE COVERSHEET A-001D INDICATES 2 HOUR FIRE SEPARATION
 BETWEEN THE 1ST FLOOR MERCANTILE OCCUPANCY AND THE 2ND
 FLOOR R2 OCCUPANCY. PLEASE PROVIDE THE FLOOR CEILING
 ASSEMBLY PROVIDING THE 2 HOUR FIRE RATING AS REQUIRED
 BY TABLE 707.3.10 FIRE-RESISTANCE RATING REQUIREMENTS
 FOR HORIZONTAL ASSEMBLIES BETWEEN FIRE AREAS. 2HRS.
  
 11B) SHEET A-102D THE CEILING PLAN HAS A CEILING LABEL
 DESIGNATED CLG-4 ? (2) LAYERS OF 5/8 INCH TYPE X GYPSUM
 ON THE CEILING THERE ARE OTHER TAGS SUCH AS CLG-3 NEW
 ACOUSTICAL CEILING 2 X2 CEILING TILE GRID. IS THERE NO
 HORIZONTAL FIRE ASSEMBLY SEPARATING THE OCCUPANCIES
 ABOVE THIS DROP CEILING? FBC-B TABLE 707.3.10.
  
 12) ON THE PERMIT APPLICATION BOTH SIGNATURES ARE
 NEEDED, THE OWNER AND SIGNATURE OF THE QUALIFIER FOR
 THE CONTACTOR. 105.1 PERMIT REQUIRED.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved