| Plan Review Notes For Permit 17020345 |
| Permit Number |
17020345 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-13 11:40:06 | 1) SHTS.A-1.10A, 1A-1.10B, 1A-5.30 - THE TOILET ROOM IN | | | THE ACTIVITY ROOM IS CONSIDERED COMMON AREA/COMMON USE | | | AND SHALL COMPLY WITH THE 2010 FBC-ACCESSIBILTY SEC. | | | 604.3, 604.3.2. - REQUIREMENTS FOR CLEAR FLOOR SPACE | | | FOR THE FIXTURES. THE MINIMUM CLEAR FLOOR SPACE WIDTH | | | FOR THE WATER CLOSET SHALL BE 60 INCHES.THE LAVATORY | | | CANNOT ENCROACH INTO THIS CLEAR FLOOR SPACE. THIS WOULD | | | REQUIRE THAT THE MINIMUM WIDTH OF THE TOILET ROOM TO BE | | | 85 INCHES WIDE IF BUILT PERFECT. 86 INCHES ALLOWS FOR | | | TOLERANCE. THIS WAS ALSO SHOWN ON THE ORIGINAL PLAN | | | SUBMITTAL. IF THERE IS AN EXCEPTION IN THE CODE THAT | | | DOES NOT REQUIRE THIS TOILET ROOM TO COMPLY, PLEASE | | | SUBMIT SUCH JUSTIFICATION FOR REVIEW. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|