| Plan Review Notes For Permit 17020341 |
| Permit Number |
17020341 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-10 11:52:19 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020341 | | | 2/10/17 | | | | | | 1) SHEET M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN | | | OR RELOCATE THE FLEX SCHEDULE FROM SHEET M6.1. | | | | | | 2) M2.1, KEY NOTE #2: PLEASE RELOCATE THE TWO ZONE | | | DAMPERS IN THE EXAM AND ADULT RECEPTION ROOMS INTO THE | | | ADJACENT TENANT SPACES THEY WILL BE SERVING IN ORDER TO | | | PROVIDE ACCESS FOR SERVICE AND REPLACEMENT- SECTION | | | 306.1 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|