Plan Review Notes
Plan Review Notes For Permit 17020336
Permit Number 17020336
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-09 08:45:45ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) & CITY
 AMENDMENTS TO THE 2015 FBC
  
 PROJECT NAME: WALMART #4446
 JOB ADDRESS: 4225 45TH ST.
 DESCRIPTION: ALTERATION & ADDITIONS TO EXISTING CCTV
 SYSTEM
 MASTER PERMIT: 17020336
  
 PLANS FOR THE ABOVE MENTIONED PERMIT WERE REVIEWED FOR
 COMPLIANCE WITH THE CODES HEREIN DESCRIBED. FOLLOWING
 YOU WILL SEE NOTES ADDRESSING THE REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 YOUR RESUBMITTAL.
  
 1. SECTION 107.2.1.4 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT BUILDING PLANS BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. THERE IS NO SCALE INDICATION ON
 SUBMITTED PLANS.
 2. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS).
 3. THE SUBMITTED DRAWING CCTV1.0 ADDRESSES DETAILS OF
 VARIOUS PORTIONS INDICATED TO BE ON SHEET CCTV1.1 WHICH
 IS MISSING.
 4. ON THE LEGEND OR ELSEWHERE SHOW THE DEVICE COUNT.
 5. INDICATE HOW THESE DEVICES WILL BE POWERED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746, CELL: 786-970-3473
 EMAIL: [email protected] OR [email protected]
  