Plan Review Notes
Plan Review Notes For Permit 17020335
Permit Number 17020335
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-09 11:28:02ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) & CITY
 AMENDMENTS TO THE 2015 FBC
  
 ELECTRICAL PLAN REVIEW COMMENTS
  
 PROJECT NAME: KEY WEST FISH & CHICKEN
 JOB ADDRESS: 1258 PALM BEACH LAKES BLVD.
 DESCRIPTION: CHANGE OUT OF FPE PANEL
 MASTER PERMIT: 17020335
  
  
 PLANS FOR THE ABOVE MENTIONED PERMIT WERE REVIEWED FOR
 COMPLIANCE WITH THE CODES HEREIN DESCRIBED. FOLLOWING
 YOU WILL SEE NOTES ADDRESSING THE REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 YOUR RESUBMITTAL.
  
 1. THIS RISER DIAGRAM AS PROVIDED IS CONFUSING.
 REFLECTED SERVICE INDICATES 4-300KCMLS CONDUCTORS AND
 THE FEEDER FOR PANEL ?A? INDICATES 4-3/0 & 1 #6 GEC,
 YET YOU SAY THE SERVICE IS 1 PHASE. CORRECT RISER
 ACCORDINGLY
 2. PER NEC 230.7 SERVICE CONDUCTORS CAN?T SHARE RACEWAY
 WITH FEEDER CONDUCTORS.
 3. PER NEC 110.16 ARC-FAULT HAZARD WARNING LABELS SHALL
 BE REQUIRED.
 4. YOU SHALL PROVIDE LOAD CALCS FOR EACH PANEL AND
 SERVICE DISCONNECT TO ASCERTAIN PROPER CONDUCTOR
 SIZING. CONDUCTORS TO PANEL ?A? ARE ONLY GOOD FOR 160
 AMP. SERVICE CONDUCTORS ARE ONLY GOOD FOR 228 AMP.
 5. PER NEC 110.14(A) TERMINAL FOR MORE THAN ONE
 CONDUCTOR SHALL BE SO IDENTIFIED. ACCORDING TO THE
 SUBMITTED RISER DIAGRAM, DISCONNECT ?A? LOAD SIDE
 TERMINALS APPEAR TO HAVE MULTIPLE CONDUCTORS.
 6. PER NEC 250.66 THE GROUNDING ELECTRODE CONDUCTOR FOR
 THIS SERVICE SHALL BE A MINIMUM OF #4 COPPER. THE
 PROVIDED RISER DIAGRAM INDICATES #10. CORRECT
 ACCORDINGLY.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH, PH. (561) 805-6746
 EMAIL: [email protected] OR [email protected]
  